Date |
Text |
2008-09-04 08:23:40 | REVISION DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| 1. SHT P202 REVISIONS 3 & 4 WERE NOT FOUND. PLEASE |
| CLOUD ALL REVISIONS AND INDICATE REVISIONS WITH THE |
| REVISION NUMBER. SECTION 106.1.3. |
| |
| 2. SHT P202 DRINKING FOUNTAINS WERE DELETED. PER TABLE |
| 403.1 MINIMUM 2 DRINKING FOUNTAINS ARE REQUIRED. PLEASE |
| INDICATE WHERE THE REQUIRED DRINKING FOUNTAINS ARE |
| LOCATED. |
| |
| 3. SHT P300 WATER ISOMETRIC RISER DIAGRAM DOES NOT |
| REFLECT THE CHANGE IN THE FLOOR PLAN INDICATED ON SHT |
| P202 AT S1 SINK IN X-RAY ROOM 14307. PLEASE CORRELATE. |
| SECTIONS 106.1.1 & 604. |
| |
| 4. SHT P300 ALL CHANGES/REVISIONS TO THE FLOOR PLAN |
| SHALL BE SHOWN ON THE SANITARY RISER DIAGRAM. S-1 SINK |
| DOES NOT SHOW CHANGE AS WELL AS THE DELETED DRINKING |
| FOUNTAINS. PLEASE CORRELATE. SECTION 106.1.1 & TABLE |
| 710.1(2). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |