Plan Review Notes
Plan Review Notes For Permit 08020160
Permit Number 08020160
Review Stop P
Sequence Number 4
Notes
Date Text
2008-09-04 08:23:40REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P202 REVISIONS 3 & 4 WERE NOT FOUND. PLEASE
 CLOUD ALL REVISIONS AND INDICATE REVISIONS WITH THE
 REVISION NUMBER. SECTION 106.1.3.
  
 2. SHT P202 DRINKING FOUNTAINS WERE DELETED. PER TABLE
 403.1 MINIMUM 2 DRINKING FOUNTAINS ARE REQUIRED. PLEASE
 INDICATE WHERE THE REQUIRED DRINKING FOUNTAINS ARE
 LOCATED.
  
 3. SHT P300 WATER ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE CHANGE IN THE FLOOR PLAN INDICATED ON SHT
 P202 AT S1 SINK IN X-RAY ROOM 14307. PLEASE CORRELATE.
 SECTIONS 106.1.1 & 604.
  
 4. SHT P300 ALL CHANGES/REVISIONS TO THE FLOOR PLAN
 SHALL BE SHOWN ON THE SANITARY RISER DIAGRAM. S-1 SINK
 DOES NOT SHOW CHANGE AS WELL AS THE DELETED DRINKING
 FOUNTAINS. PLEASE CORRELATE. SECTION 106.1.1 & TABLE
 710.1(2).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved