2008-05-14 17:01:02AUDIT #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 5: OK
  
 6. THE SMOKE CONTROL SYSTEM FOR THIS BUILDING HAS BEEN
 TESTED, COMMISSIONED AND IS COMPLETE. A NEW RATIONAL
 ANALYSIS SUPPORTING THE DESIGN OF THE PROPOSED
 MODIFICATIONS WITHIN THIS TENANT SPACE AND A SEQUENCE
 OF OPERATIONS SHALL BE SUBMITTED PRIOR TO PERMIT
 ISSUANCE.
  
 NOTE: ONCE CONSTRUCTION IS COMPLETE AND PRIOR TO A
 CERTIFICATE OF OCCUPANCY FOR THIS SPACE, THE BUILDING
 SMOKE CONTROL SYSTEM SHALL BE RE-TESTED AND
 RE-COMMISSIONED. THE EXTENT OF THE TESTING NECESSARY TO
 DEMONSTRATE THE FUNCTIONALITY OF NEW AND EXISTING
 PORTIONS OF THE SYSTEM MUST BE COORDINATED WITH THE
 CHIEF MECHANICAL INSPECTOR, FIRE MARSHAL AND
 COMMISSIONING AGENT. ANALYSIS AND TESTING SHALL BE DONE
 IN ACCORDANCE WITH FBCB SECTION 909.
  
 7 THROUGH 11: OK
  
 12. THE NOTICE TO BUILDING OFFICIAL AFFIDAVIT WHICH WAS
 PROVIDED IS A PHOTOCOPY. PLEASE PROVIDE ORIGINAL
 DOCUMENTATION WITH ORIGINAL SIGNATURES AND NOTARY
 STAMP.
  
 NEW: A PLAN REVIEW AFFIDAVIT FROM CAPRI ENGINEERING WAS
 NOT PROVIDED FOR THE FOLLOWING MECHANICAL PAGES WITH
 THIS SUBMITTAL: M300, M600, M700, M701, M702 SIGNED
 3/11/08.
  