2008-05-14 17:01:02 | AUDIT #: 2ND |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| 1 THROUGH 5: OK |
| |
| 6. THE SMOKE CONTROL SYSTEM FOR THIS BUILDING HAS BEEN |
| TESTED, COMMISSIONED AND IS COMPLETE. A NEW RATIONAL |
| ANALYSIS SUPPORTING THE DESIGN OF THE PROPOSED |
| MODIFICATIONS WITHIN THIS TENANT SPACE AND A SEQUENCE |
| OF OPERATIONS SHALL BE SUBMITTED PRIOR TO PERMIT |
| ISSUANCE. |
| |
| NOTE: ONCE CONSTRUCTION IS COMPLETE AND PRIOR TO A |
| CERTIFICATE OF OCCUPANCY FOR THIS SPACE, THE BUILDING |
| SMOKE CONTROL SYSTEM SHALL BE RE-TESTED AND |
| RE-COMMISSIONED. THE EXTENT OF THE TESTING NECESSARY TO |
| DEMONSTRATE THE FUNCTIONALITY OF NEW AND EXISTING |
| PORTIONS OF THE SYSTEM MUST BE COORDINATED WITH THE |
| CHIEF MECHANICAL INSPECTOR, FIRE MARSHAL AND |
| COMMISSIONING AGENT. ANALYSIS AND TESTING SHALL BE DONE |
| IN ACCORDANCE WITH FBCB SECTION 909. |
| |
| 7 THROUGH 11: OK |
| |
| 12. THE NOTICE TO BUILDING OFFICIAL AFFIDAVIT WHICH WAS |
| PROVIDED IS A PHOTOCOPY. PLEASE PROVIDE ORIGINAL |
| DOCUMENTATION WITH ORIGINAL SIGNATURES AND NOTARY |
| STAMP. |
| |
| NEW: A PLAN REVIEW AFFIDAVIT FROM CAPRI ENGINEERING WAS |
| NOT PROVIDED FOR THE FOLLOWING MECHANICAL PAGES WITH |
| THIS SUBMITTAL: M300, M600, M700, M701, M702 SIGNED |
| 3/11/08. |
| |