Plan Review Notes
Plan Review Notes For Permit 08020160
Permit Number 08020160
Review Stop E
Sequence Number 2
Notes
Date Text
2008-05-20 12:08:18** DENIED2ND AUDIT**
  
 ** PLEASE SEE SOME ITEMS STILL REMAIN FROM PREVIOUS
 AUDIT.
  
 1) NOTE: PLEASE SEE AFFIDAVITS ARE NOW ONLY BEING
 SUBMITTED. PLEASE SEE THESE ARE BEING MADE OUT TO
 BALFOUR CONCORD. THE CONTRACTOR ON THIS PROJECT IS
 BALFOUR/BEATTY.
 PLEASE COORDINATE.
 PLEASE ALSO SEE NOTICE TO BUILDING OFFICIAL SUBMITTED
 WHICH IS IN FACT PHOTO-COPIES AND ARE NOT ORIGINAL.
 THESE CONTAIN STAMPS *REVIEWED FOR COMPLIANCE8 FROM THE
 PRIVATE PROVIDER.
 PLEASE ONLY INCLUDE ORIGINAL DOCUMENTS AND PLEASE BE
 SURE TO FILL OUT WITH THE CORRECT CONTRACTOR.
  
 2) NOTE: PLEASE SUBMIT PLANS IN A NEAT AND ORDERLY
 FASHION WITH STAPLES SECURING ALL SHEETS TOGETHER.
 SEVERAL SHEETS IN THE BACK OF THE SETS WERE NOT SECURED
 TO THE REST OF THE SET. PLEASE ALSO DO NOT ATTACHED ALL
 OTHER DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS.
 PLEASE SUBMIT THESE IN SOME SORT OF BINDER/FOLDER WHICH
 THESE DOCUMENTS MAY BE READILY GONE OVER.
 PLEASE KNOW THESE WERE DETACHED AND PLACED INTO
 SEPARATE CLIPS AT THIS TIME.
 PLEASE ALSO KNOW DUE TO SOME COMMENTS BELOW SOME
 DOCUMENTS MAY ALSO BE RETAINED BY THIS OFFICE.
 FBC 106.1.2, 106.1, 106.1.3, 106.5 FOR ADDITIONAL
 INFORMATION, SUBMITTING OF PLANS, RECORD DOCUMENTS.
  
 3) NOTE: PLEASE SEE THE FLORIDA ENERGY EFFICIENCY CODE
 CALCULATIONS SUBMITTED ARE NOT CODE COMPLIANT.
 PLEASE SEE 13-400.3.A AS THE INCORRECT VERSION WAS
 SUBMITTED. THE VERSION SUBMITTED IS 3.0 WHEN THE CODE
 REQUIRES VERSION 2.5 WHEN USING FLA-COM PROGRAM.
 IN ANY CASE METHOD *A* MAY NOT BE USED AS THIS IS A
 TENANT SPACE BUILD OUT IN A BUILDING AND IS NOT A *
 WHOLE BUILDING*. PLEASE SEE THE DEFINITIONS IN THE FBC
 13-400.0.A. PLEASE PROVIDE INFORMATION AND
 DOCUMENTATION EXPLAINING HOW METHOD *A* SUBMITTED IS
 BEING USED.
  
 4) NOTE: PLEASE SEE THE SUBMITTED CALCULATIONS WERE
 ALSO STAMPED AS BEING CODE COMPLIANT BY THE PRIVATE
 PROVIDER WHEN IN FACT THESE ARE NOT SIGNED, DATED OR
 SEALED BY ANY ENGINEER OF RECORD. PLEASE SEE 13-103.1
 AS THIS SCOPE OF WORK IS REQUIRED TO BE DONE BY A
 LICENSED ENGINEER. PLEASE SEE THE SUBMITTED DOCUMENTS
 WERE SIGNED BY AN INDIVIDUAL WHICH DOES NOT LIST ANY
 LICENSE INFORMATION. IN FACT THE DOCUMENTS SUBMITTED
 CLEARLY SHOW A (PHOTO-COPIED SIGNATURE* FROM A
 *PREPARER* WHICH IS NOT LISTED AS A PE AND NOT AS ONE
 OF THE DESIGNERS OF RECORD. THIS IS THE SAME ON ALL
 THREE SETS SUBMITTED.
 WHEN SIGNING, DATING AND SEALING ANY DOCUMENTS AN
 ENGINEER MUST USE AN ORIGINAL SIGNATURE.
 FS 471.025, FAC 61G15-23.002
  
 5) NOTE: ** PLEASE SEE THE LIGHTING CALCULATIONS ALSOO
 SUBMITTED ARE IN FACT PHOTO-METRIC LEVELS WHICH ARE NOT
 LIGHTING PERFORMANCE CALCULATIONS REQUIRED PER FBC
 13-415.2, 13-415.2.ABC.1.1, .1.2. PLEASE KNOW THESE
 SHALL NOT BE USED IN LIEU OF REQUIRED CALCULATIONS.
 PLEASE KNOW THESE WERE GONE OVER IN MEETING HELD BEFORE
 RESUBMITTING PLANS HOWEVER THESE ARE STILL BEING
 SUBMITTED.
 ** FOR INFORMATION:
 PLEASE KNOW ANY DOCUMENTS SUBMITTED AND PART OF THE
 DESIGN OF A PROJECT BY THE ENGINEER SHALL BE SIGNED,
 DATED, SEALED CONTAINING TITLE BLOCKS ETC.
  
 6) NOTE: PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS MEETING THE FLORIDA BUILDING CODE
 13-415.2, 13-415.2.ABC.1.1, .1.2.
 THE LIGHTING DENSITIES LISTED ON SHEET E200 ARE NOT
 COMPLETE. PLEASE COMPLETE AS SEE LEVELS IN TABLES IN
 THE FBC. PLEASE BE SURE THE LIGHTING FIXTURE LEGEND
 COORDINATES WITH CALCULATIONS, NUMBERS OF FIXTURES,
 TYPES OF FIXTURES ETC TO COORDINATE CODE COMPLIANCE.
 ** PLEASE KNOW SOME LEVELS SHOWN IN THE SPACE BY SPACE
 EXCEED LEVELS IN 13-415.2.B
  
 7) NOTE: PLEASE SEE MISSING MAXIMUM TIMES ON OVER RIDES
 AND OCCUPANCY SENSOR DEVICES. THE RESPONSE MENTIONS TO
 SEE E-100 AND E200 HOWEVER THE REVISED DEVICES, OVER
 RIDES AND OCCUPANCY SENSOR SWITCHES DO NOT INDICATE ANY
 TIMES.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SOME DEVICES ON PLANS ARE NOT ON SYMBOL
 LEGEND: FOR EXAMPLE PLEASE SEE READING ROOM AND OUTSIDE
 READING ROOM IN HALL AND SOME OTHER LOCATIONS WHICH
 SHOW A S IN A BOX HOWEVER NO OTHER DESIGNATION IS
 SHOWN. THERE IS NO S IN A SQUARE BOX ON SYMBOL LEGEND.
 WHICH DEVICE IS THIS?
 PLEASE COMPLETE.
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]