Plan Review Notes
Plan Review Notes For Permit 08020160
Permit Number 08020160
Review Stop P
Sequence Number 1
Notes
Date Text
2008-02-11 12:43:18AUDIT DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY MUNICIPAL CODE
  
 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE
 NUMBER, (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN
 THE TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS
 481.219, 481.2055.
  
 2. PER TABLE 403.1 2 DRINKING FOUNTAINS ARE REQUIRED.
 PLEASE INDICATE THE LOCATION OF EACH REQUIRED DRINKING
 FOUNTAIN. SECTION 106.1.1.
  
 3. SUBMIT DETAILS FOR THE ACCESSIBLE TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
  
 4. SHT A0201 TOILET ROOMS 14-310 & 14-105 THE DOOR
 SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE. SECTION 11-4.22.3.
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 6. SHT A1002 TOILET ROOMS 14-104, 14-105 & 14-310 STATE
 "CT-2 AT WET WALL, PT ALL OTHER WALLS". PER SECTION
 1210.2 WALLS WITHIN 2 FEET (610 MM) OF URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE
 FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS
 NOT ADVERSELY AFFECTED BY MOISTURE.
 PAINTED SURFACES DOES NOT MEET THE REQUIREMENT FOR A
 "HARD SURFACE".
  
 7. SUBMIT A DETAIL FOR THE LOUNGE SINK SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
  
 8. SHT P001 INDICATE THE LISTING NUMBER FOR THE FLOOR
 AND WALL PENETRATIONS. SECTION 712.3.1.2. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL
 PENETRATED.--ALSO THE FLOOR SLEEVE DETAIL INDICATES
 THAT THE SLEEVE SHALL BE 1" ABOVE THE FLOOR. WITH THE
 RISER CLAMP SITTING ON THE SLEEVE, PLEASE SUBMIT A
 DETAIL SHOWING HOW THE SLEEVE IS ATTACHED TO THE FLOOR
 AND INDICATE THE MATERIAL AND GUAGE FOR THE SLEEVE.
 SECTION 308.9.
  
 9. SHT P001 WATER HEATER WH-1 PIPING DETAIL. THE VACUUM
 RELIEF VALVE IS SHOWN IN THE HOT WATER LINE. THE VALVE
 SHALL BE INSTALLED IN THE COLD WATER LINE PER SECTION
 504.2.--FLOOR DRAINS ARE NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. A FLOOR SINK OR HUB DRAIN IS REQUIRED.
 SECTIONS 802.3 & 802.3.2. (MAKE CHANGES TO PIPING &
 RISER DIAGRAMS).--SUBMIT CALCULATIONS FOR THE SIZE
 OF THE EXPANSION TANK, OR PROVIDE MANUF. TABLES
 INDICATING THE MODEL NUMBER AND MAXIMUM GALLONS FOR
 MODEL NUMBER FOR THE EXPANSION TANK TO VERIFY CORRECT
 SIZE. SECTION 607.3.2.
  
 10. SHT P202 CONDENSATE SHALL NOT DRAIN TO THE SANITARY
 SYSTEM. MUNICIPAL CODE ARTICLE III SECTION
 90-125(B)(5). CONDENSATE SHALL CONNECT TO THE
 CONDENSATE RISERS AND DRAIN SEPARATELY.
  
 11. SHT P202 SPECIFIC NOTES #3 IS NOT FOUND ON THE
 FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 12. SHT P202 SHOWS 2 COLD WATER SUPPLIES TO THE SINK IN
 ROOM 14-130. HOT WATER IS REQUIRED PER SECTION 607.1.
  
 13. SHT P202 WATER & VENT DROPS TO SINKS IN ROOMS
 14-010, 14-100 & 14-106 AS WELL AS THE WATER & VENT
 DROPS BETWEEN THE TOILET ROOMS ARE SHOWN DROPING DOWN
 OUT OF THE WALL. PLEASE CLARIFY.
  
 14. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN F-7
 DOES NOT REFLECT THE FLOOR PLAN. THE EXTENTION OF THE
 FUTURE SANT IS NOT SHOWN ON THE FLOOR PLAN, THE FLOOR
 PLAN SHOWS OFFSETS IN THE 4" BRANCH LINE TO THE TOILET
 ROOM AND THE 1-1/2" LINE TO THE S-1 SINK. OFFSETS ARE
 NOT SHOWN ON THE RISER DIAGRAM. THE LINE TO THE S-1
 SINK IS INDICATED AS 1-1/2" ON THE FLOOR PLAN, BUT 2"
 ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1.
  
 15. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN L-7
 DOES NOT REFLECT THE FLOOR PLAN, NOR DOES IS MEET CODE.
 THE HUB DRAIN FOR THE A/C CONDENSATE IS NOT APPROVED
 PER MUNICIPAL CODE ARTICLE III SECTION 90-125(B)(5).
 PLEASE DELETE.
  
 16. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN L-5
 DOES NOT REFLECT THE FLOOR PLAN. THE S-1 SINK AT THE
 SOUTH SIDE OF COLUMN SHOWS INDIVICUAL VENTS ON THE
 FLOOR PLAN, BUT SINGLE VENT ON THE RISER DIAGRAM.--
 FLOOR PLAN SHOWS THE SANT. FOR THE SINK RUNNING SOUTH
 OF THE 3" STACK, BUT THE RISER DIAGRAM SHOWS THE PIPING
 RUNNING EAST THEN SOUTH.--THE 1ST RISER ON THE
 BRANCH LINE TO THE WEST, (FOR ROOMS 14-140 & 14-142),
 RISER IS SHOWN CONNECTING TO THE MAIN LINE RUNNING
 NORTH & SOUTH ON THE FLOOR PLAN, BUT ON THE WEST BRANCH
 LINE ON THE RISER DIAGRAM. OTHER RISERS ON THE WEST
 BRANCH LINE DO NOT REFLECT THE FLOOR PLAN.--THE 3"
 LINE CAPPED FOR THE FUTURE SHOWN ON THE FLOOR PLAN IS
 NOT SHOWN ON THE RISER DIAGRAM.--VENTING DOES NOT
 REFLECT THE FLOOR PLAN FOR THE FUTURE VENT AND THE SINK
 IN ROOM 14-161.--THE BRANCH LINES AT THE UPSTREAM
 END OF THE RISER DIAGRAM SHOW 4 RISERS TO THE WEST AND
 1 RISER ON THE EAST BRANCH ON THE FLOOR PLAN, BUT SHOW
 2 RISERS ON EACH BRANCH ON THE RISER DIAGRAM. PLEASE
 CORRELATE AND SUBMIT THE RISER DIAGRAMS THAT REFLECT
 THE FLOOR PLAN. SECTIONS 106.1.1 & TABLE 710.1(2).
  
 17. SUBMIT AN ISOMETRIC WATER RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS ETC.
 SECTIONS 106.3.5.1.3 & 604.
  
 18. SUBMIT AN ISOMETRICCONDENSATE RISER DIAGRAM
 SHOWING ALL PIPE SIZES TRAPS, VENTS, POINT OF
 CONNECTION TO THE CONDENSATE RISER ETC. SECTION
 106.3.5.1.3.
  
 19. PRIVATE PROVIDER AFFIDAVIT PROJECTS-IN ADDITION
 TO THE SIGNED AFFIDAVIT FROM THE PRIVATE PROVIDER, WE
 MUST ALSO CHECK TO SEE THAT THE OWNER HAS SIGNED AN
 OWNER ACKNOWLEDGEMENT LETTER PER FLORIDA STATUTE,
 SECTION 553.791(4)(C).THE LETTER IS THE MEANS BY
 WHICH THE OWNER ACKNOWLEDGES THAT THEY ARE AWARE THAT
 THEIR PROJECT IS BEING REVIEWED (AND IF RELEVANT,
 INSPECTED) UNDER THE PRIVATE PROVIDER PROVISIONS OF
 FLORIDA STATUTE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved