Date |
Text |
2008-02-11 12:43:18 | AUDIT DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| CITY MUNICIPAL CODE |
| |
| 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE |
| NUMBER, (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN |
| THE TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS |
| 481.219, 481.2055. |
| |
| 2. PER TABLE 403.1 2 DRINKING FOUNTAINS ARE REQUIRED. |
| PLEASE INDICATE THE LOCATION OF EACH REQUIRED DRINKING |
| FOUNTAIN. SECTION 106.1.1. |
| |
| 3. SUBMIT DETAILS FOR THE ACCESSIBLE TOILET ROOMS |
| SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & |
| 11-4.22 WITH ALL SUBSECTIONS. |
| |
| 4. SHT A0201 TOILET ROOMS 14-310 & 14-105 THE DOOR |
| SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR |
| ANY FIXTURE. SECTION 11-4.22.3. |
| |
| 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING |
| COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| WELL AS 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| DIFFICULTY BENDING OR STOOPING. |
| |
| 6. SHT A1002 TOILET ROOMS 14-104, 14-105 & 14-310 STATE |
| "CT-2 AT WET WALL, PT ALL OTHER WALLS". PER SECTION |
| 1210.2 WALLS WITHIN 2 FEET (610 MM) OF URINALS AND |
| WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE |
| FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE |
| MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS |
| NOT ADVERSELY AFFECTED BY MOISTURE. |
| PAINTED SURFACES DOES NOT MEET THE REQUIREMENT FOR A |
| "HARD SURFACE". |
| |
| 7. SUBMIT A DETAIL FOR THE LOUNGE SINK SHOWING |
| COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS. |
| |
| 8. SHT P001 INDICATE THE LISTING NUMBER FOR THE FLOOR |
| AND WALL PENETRATIONS. SECTION 712.3.1.2. THROUGH |
| PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN |
| ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM |
| POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN |
| THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL |
| PENETRATED.--ALSO THE FLOOR SLEEVE DETAIL INDICATES |
| THAT THE SLEEVE SHALL BE 1" ABOVE THE FLOOR. WITH THE |
| RISER CLAMP SITTING ON THE SLEEVE, PLEASE SUBMIT A |
| DETAIL SHOWING HOW THE SLEEVE IS ATTACHED TO THE FLOOR |
| AND INDICATE THE MATERIAL AND GUAGE FOR THE SLEEVE. |
| SECTION 308.9. |
| |
| 9. SHT P001 WATER HEATER WH-1 PIPING DETAIL. THE VACUUM |
| RELIEF VALVE IS SHOWN IN THE HOT WATER LINE. THE VALVE |
| SHALL BE INSTALLED IN THE COLD WATER LINE PER SECTION |
| 504.2.--FLOOR DRAINS ARE NOT AN APPROVED INDIRECT |
| WASTE RECEPTOR. A FLOOR SINK OR HUB DRAIN IS REQUIRED. |
| SECTIONS 802.3 & 802.3.2. (MAKE CHANGES TO PIPING & |
| RISER DIAGRAMS).--SUBMIT CALCULATIONS FOR THE SIZE |
| OF THE EXPANSION TANK, OR PROVIDE MANUF. TABLES |
| INDICATING THE MODEL NUMBER AND MAXIMUM GALLONS FOR |
| MODEL NUMBER FOR THE EXPANSION TANK TO VERIFY CORRECT |
| SIZE. SECTION 607.3.2. |
| |
| 10. SHT P202 CONDENSATE SHALL NOT DRAIN TO THE SANITARY |
| SYSTEM. MUNICIPAL CODE ARTICLE III SECTION |
| 90-125(B)(5). CONDENSATE SHALL CONNECT TO THE |
| CONDENSATE RISERS AND DRAIN SEPARATELY. |
| |
| 11. SHT P202 SPECIFIC NOTES #3 IS NOT FOUND ON THE |
| FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 12. SHT P202 SHOWS 2 COLD WATER SUPPLIES TO THE SINK IN |
| ROOM 14-130. HOT WATER IS REQUIRED PER SECTION 607.1. |
| |
| 13. SHT P202 WATER & VENT DROPS TO SINKS IN ROOMS |
| 14-010, 14-100 & 14-106 AS WELL AS THE WATER & VENT |
| DROPS BETWEEN THE TOILET ROOMS ARE SHOWN DROPING DOWN |
| OUT OF THE WALL. PLEASE CLARIFY. |
| |
| 14. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN F-7 |
| DOES NOT REFLECT THE FLOOR PLAN. THE EXTENTION OF THE |
| FUTURE SANT IS NOT SHOWN ON THE FLOOR PLAN, THE FLOOR |
| PLAN SHOWS OFFSETS IN THE 4" BRANCH LINE TO THE TOILET |
| ROOM AND THE 1-1/2" LINE TO THE S-1 SINK. OFFSETS ARE |
| NOT SHOWN ON THE RISER DIAGRAM. THE LINE TO THE S-1 |
| SINK IS INDICATED AS 1-1/2" ON THE FLOOR PLAN, BUT 2" |
| ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION |
| 106.1.1. |
| |
| 15. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN L-7 |
| DOES NOT REFLECT THE FLOOR PLAN, NOR DOES IS MEET CODE. |
| THE HUB DRAIN FOR THE A/C CONDENSATE IS NOT APPROVED |
| PER MUNICIPAL CODE ARTICLE III SECTION 90-125(B)(5). |
| PLEASE DELETE. |
| |
| 16. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN L-5 |
| DOES NOT REFLECT THE FLOOR PLAN. THE S-1 SINK AT THE |
| SOUTH SIDE OF COLUMN SHOWS INDIVICUAL VENTS ON THE |
| FLOOR PLAN, BUT SINGLE VENT ON THE RISER DIAGRAM.-- |
| FLOOR PLAN SHOWS THE SANT. FOR THE SINK RUNNING SOUTH |
| OF THE 3" STACK, BUT THE RISER DIAGRAM SHOWS THE PIPING |
| RUNNING EAST THEN SOUTH.--THE 1ST RISER ON THE |
| BRANCH LINE TO THE WEST, (FOR ROOMS 14-140 & 14-142), |
| RISER IS SHOWN CONNECTING TO THE MAIN LINE RUNNING |
| NORTH & SOUTH ON THE FLOOR PLAN, BUT ON THE WEST BRANCH |
| LINE ON THE RISER DIAGRAM. OTHER RISERS ON THE WEST |
| BRANCH LINE DO NOT REFLECT THE FLOOR PLAN.--THE 3" |
| LINE CAPPED FOR THE FUTURE SHOWN ON THE FLOOR PLAN IS |
| NOT SHOWN ON THE RISER DIAGRAM.--VENTING DOES NOT |
| REFLECT THE FLOOR PLAN FOR THE FUTURE VENT AND THE SINK |
| IN ROOM 14-161.--THE BRANCH LINES AT THE UPSTREAM |
| END OF THE RISER DIAGRAM SHOW 4 RISERS TO THE WEST AND |
| 1 RISER ON THE EAST BRANCH ON THE FLOOR PLAN, BUT SHOW |
| 2 RISERS ON EACH BRANCH ON THE RISER DIAGRAM. PLEASE |
| CORRELATE AND SUBMIT THE RISER DIAGRAMS THAT REFLECT |
| THE FLOOR PLAN. SECTIONS 106.1.1 & TABLE 710.1(2). |
| |
| 17. SUBMIT AN ISOMETRIC WATER RISER DIAGRAM SHOWING ALL |
| PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS ETC. |
| SECTIONS 106.3.5.1.3 & 604. |
| |
| 18. SUBMIT AN ISOMETRICCONDENSATE RISER DIAGRAM |
| SHOWING ALL PIPE SIZES TRAPS, VENTS, POINT OF |
| CONNECTION TO THE CONDENSATE RISER ETC. SECTION |
| 106.3.5.1.3. |
| |
| 19. PRIVATE PROVIDER AFFIDAVIT PROJECTS-IN ADDITION |
| TO THE SIGNED AFFIDAVIT FROM THE PRIVATE PROVIDER, WE |
| MUST ALSO CHECK TO SEE THAT THE OWNER HAS SIGNED AN |
| OWNER ACKNOWLEDGEMENT LETTER PER FLORIDA STATUTE, |
| SECTION 553.791(4)(C).THE LETTER IS THE MEANS BY |
| WHICH THE OWNER ACKNOWLEDGES THAT THEY ARE AWARE THAT |
| THEIR PROJECT IS BEING REVIEWED (AND IF RELEVANT, |
| INSPECTED) UNDER THE PRIVATE PROVIDER PROVISIONS OF |
| FLORIDA STATUTE. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |
| |