Plan Review Notes
Plan Review Notes For Permit 08020160
Permit Number 08020160
Review Stop M
Sequence Number 1
Notes
Date Text
2008-02-15 11:22:31REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M200: THERE ARE SEVERAL LOCATIONS THROUGHOUT THIS
 FLOOR PLAN WHERE DUCTS ARE SHOWN PENETRATING FIRE
 RESISTANCE RATED WALL ASSEMBLIES WITHOUT ANY OPENING
 PROTECTIVE. EXAMPLE: FAN ROOM 14-312 IS FULLY ENCLOSED
 IN TYPE 2A WALLS, WHICH CARRY A 1-HOUR RATING AS SHOWN
 ON PG A1002. THERE ARE AT LEAST TWO DUCTS EXITING THIS
 ROOM WITHOUT FIRE DAMPERS AT THE WALL PENETRATIONS.
 THERE ARE MULTIPLE OTHER INSTANCES. PLEASE COORDINATE
 FLOOR PLANS FOR ARCHITECTURAL AND MECHANICAL, SHOWING
 OPENING PROTECTIVES WHERE REQUIRED IN ACCORDANCE WITH
 FBC, M 607.5.
  
 2. M200: CONVERSELY, THERE IS A FIRE DAMPER SHOWN IN A
 24X10 DUCT PENETRATING A TYPE 6 WALL (NON RATED
 ACCORDING TO PG A1002) NEAR COLUMN LINE F. A FIRE
 DAMPER IS SHOWN AT THIS LOCATION. FIRE DAMPERS ARE TO
 BE INSTALLED IN ACCORDANCE WITH THEIR LISTING PER FBC,
 M 607.2. THE SPECIFIC BRAND OF FIRE DAMPER IS NOT KNOWN
 AT THIS TIME BUT THE LISTING LIKELY REQUIRES THAT IT BE
 INSTALLED IN A RATED ASSEMBLY. AGAIN, PLEASE COORDINATE
 MECHANICAL AND ARCHITECTURAL FLOOR PLANS ACCORDINGLY.
  
 3. M200: EF-1 AND SF-1 SHOW NEW LOUVERS TO BE INSTALLED
 IN EXTERIOR WALLS. LOUVERS ARE CLASSIFIED AS PANEL
 WALLS PER FAC RULE 9B-72 AND AS SUCH, PRODUCT APPROVAL
 IS REQUIRED. PROVIDE PRODUCT APPROVAL FOR BUILDING PLAN
 REVIEW. PRODUCT APPROVALS SHALL BE APPROVED IN WRITING
 BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THIS
 OFFICE FOR REVIEW IN ACCORDANCE WITH FBC 106.3.3.
  
 4. M200: THE LOUVER OPENING FOR EF-1 MAY BE IN A 2-HOUR
 RATED EXTERIOR WALL IN ACCORDANCE WITH FBC TABLE 602.
 BASED ON THE DOCUMENTATION PROVIDED, IT IS UNCLEAR AS
 TO THE ALLOWABLE PERCENTAGE OF UNPROTECTED OPENINGS IN
 THIS WALL. OUTDOOR AIR EXHAUST AND INTAKE OPENINGS
 LOCATED IN EXTERIOR WALLS SHALL MEET THE PROVISIONS FOR
 EXTERIOR WALL OPENING PROTECTIVES IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING PER FBC, M 401.6.
 IF A CLAIM FOR ALLOWED UNPROTECTED OPENINGS IS MADE,
 PLEASE PROVIDE ALL NECESSARY INFORMATION AND
 CALCULATIONS FOR BUILDING PLAN REVIEW.
  
 5. M200: A 44X12 ?SMOKE CONTROL TRANSFER OPENING IN
 WALL W/ SMOKE DAMPER? IS SHOWN IN WALL ON NORTH SIDE OF
 SPACE. THERE IS NOT INDICATION THAT THIS IS ALSO A FIRE
 DAMPER. A FIRE DAMPER IS REQUIRED AT THIS LOCATION AS
 IT IS LOCATED IN A 1-HOUR RATED WALL AS INDICATED ON
 ARCHITECTURAL FLOOR PLAN. ALSO, BY WHAT MEANS WILL THIS
 SMOKE DAMPER BE CONTROLLED? SMOKE DAMPERS SHALL BE
 ACTUATED BY ONE OF THE METHODS LISTED IN FBC, M
 607.3.2.1. THIS DAMPER IS NOT PART OF THE BASE BUILDING
 SMOKE CONTROL SYSTEM. WILL THE BASE BUILDING DESIGN BE
 REVISED TO INCORPORATE THIS NEW SMOKE DAMPER?
  
 6. M200: RELATED TO COMMENT #5 ABOVE, SPECIFIC NOTE #6
 ON PLAN CALLS FOR SMOKE DAMPERS TO BE INSTALLED IN
 DUCTS IN VARIOUS LOCATIONS THROUGHOUT THE FLOOR PLAN,
 INCLUDING SUPPLY AND RETURN DUCTS WHICH ARE PART OF A
 ?SMOKE REMOVAL SYSTEM IN DUCT.?
 A) EXISTING PAC-1 SUPPLY AND RETURN DUCT IS BEING SHOWN
 AS PART OF A SMOKE REMOVAL SYSTEM. PAC-1 HAS NO ROLE IN
 THIS BUILDING?S SMOKE CONTROL SYSTEM OTHER THAN IT WILL
 BE SHUT DOWN DURING SMOKE CONTROL MODE.
 B) A RATIONAL ANALYSIS OF THIS BUILDING?S SMOKE CONTROL
 SYSTEM HAS BEEN PERFORMED AND SUBMITTED AS PART OF THE
 BASE BUILDING?S PERMIT RECORD. ANY MODIFICATIONS TO THE
 SMOKE CONTROL SYSTEM (AS PROPOSED BY THIS TENANT) MUST
 BE INCORPORATED INTO THE RATIONAL ANALYSIS, INCLUDING
 ANY ADDITIONAL DAMPERS WHICH NEED TO BE CONTROLLED BY
 THE SYSTEM IN ACCORDANCE WITH FBC, M 513.4.
 C) ITD ROOM 14-121 IS SHOWN ON FLOOR PLAN TO 1-HOUR
 RATED WITH TYPE 2A WALLS EXTENDING TO THE UNDERSIDE OF
 THE DECK ABOVE ON THREE SIDES. ONE OF THESE WALLS IS
 SHOWN ON FLOOR PLAN BISECTING THE 60X20 OUTLET OF THE
 SUPPLY DUCT FOR THE BUILDING SMOKE CONTROL SYSTEM. THIS
 WOULD BE AN IMPEDIMENT TO MOST OF THE AIR, TRAPPING IT
 IN THE ITD ROOM AND PREVENTING THE AIR FROM
 PRESSURIZING THE ENTIRE FLOOR, WHICH IS ITS PURPOSE.
 PLEASE SHOW HOW THE RATING OF THIS ROOM IS TO BE
 ACHIEVED WITHOUT DEFEATING THE BUILDING SMOKE CONTROL
 SYSTEM. ADDITIONALLY, THE REQUIRED RATING OF THE TYPE
 2A WALL CAN NOT BE MAINTAINED AS IT CROSSES THE OPEN
 END OF THE 60X20 DUCT.
 D) WEST OF THE SERVICE ELEVATOR THERE IS AN
 UNIDENTIFIED ENCLOSED AREA SURROUNDED BY TEMPORARY
 CORRIDOR 14-036. THIS AREA ENCLOSES THE EXHAUST INLET
 FOR THE BUILDING SMOKE CONTROL SYSTEM. THIS ENCLOSURE
 CREATES A PLENUM SPACE TO BE USED BY THE EXHAUST
 PORTION OF THE BUILDING SMOKE CONTROL SYSTEM. THIS
 SPACE IS NOT PART OF THE BASE BUILDING DESIGN AS IT IS
 NOT SHOWN ON THE BASE BUILDING PLANS. THE WALL TYPES
 AND FINISHES ARE NOT KNOWN AS THEY ARE NOT IDENTIFIED
 ON THE ARCHITECTURAL FLOOR PLAN FOR THE TENANT SPACE.
 THERE ARE TRANSFER DUCTS AND SMOKE DAMPERS SHOWN
 FEEDING THIS PLENUM SPACE WHICH ARE ALSO NOT PART OF
 THE CURRENT SMOKE CONTROL SYSTEM DESIGN. PLEASE CLARIFY
 THE INTENT, IDENTIFY IF THESE WALLS CARRY ANY SORT OF
 RATING AND DETERMINE IF THIS DESIGN WILL BE
 INCORPORATED INTO THE BASE BUILDING DESIGN. FBC, M
 513.2 AND 513.4
  
 7. M200: SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL
 FOR PROPOSED NEW AC-1 IN ITD ROOM IN COMPLIANCE WITH
 FBC, M 307.2.2.
  
 8. PROVIDE DETAIL FOR A LISTED THROUGH-PENETRATION
 FIRESTOP SYSTEM TO BE USED WHERE CONDENSER AND/OR
 CONDENSATE PIPING IS TO PENETRATE FIRE RESISTANCE RATED
 WALL ASSEMBLIES IN ACCORDANCE WITH FBC 712.3.
  
 9. M500: FIRE DAMPER DETAILS, THESE DETAILS ARE LIKELY
 TO BE IN CONFLICT WITH FIRE DAMPER MANUFACTURER?S
 INSTALLATION INSTRUCTIONS. FIRE DAMPERS, SMOKE DAMPERS
 AND COMBINATION FIRE/SMOKE DAMPERS LOCATED WITHIN AIR
 DISTRIBUTION AND SMOKE CONTROL SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THIS
 SECTION, AND THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS AND LISTING PER FBC, M 607.2. COORDINATE
 DETAIL ON PLANS WITH MANUFACTURER?S INSTALLATION
 INSTRUCTIONS OR PROVIDE A NOTE ON PLANS INDICATING THAT
 IN THE EVENT OF A CONFLICT THE MANUFACTURER?S
 INSTRUCTIONS SHALL PREVAIL.
  
 10. M200 AND M701: SF2 SHALL BE PROVIDED WITH A DUCT
 SMOKE DETECTOR. SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY GREATER THAN
 2,000 CFM IN THE SUPPLY AIR DUCT IN ACCORDANCE WITH
 FBC, M 606.2.1.
  
 11. M701: SEQUENCE OF OPERATION DOES NOT HAVE ANY
 INDICATION THAT SMOKE DETECTORS IN THE SUPPLY DUCT HAVE
 BEEN TAKEN INTO ACCOUNT AS ONLY THE RETURN SMOKE
 DETECTORS ARE SHOWN IN THE SEQUENCE AND DIAGRAMS. NOTE:
 FBC, M 606.2.1 REQUIRES DETECTORS AT A MINIMUM IN THE
 SUPPLY DUCT AND 606.2.2 REQUIRES THEM ADDITIONALLY IN
 THE RETURN DUCT. THE SUPPLY DETECTORS SHALL ALSO
 INITIATE A FAN SHUT-DOWN AND INITIATE AN ALARM SIGNAL
 IN ACCORDANCE WITH THIS SECTION.
  
 12. THESE PLANS HAVE BEEN REVIEWED AND SUBMITTED UNDER
 THE PRIVATE PROVIDER SYSTEM AS ESTABLISHED UNDER FS
 553.791. THIS STATUTE REQUIRES AN AFFIDAVIT FROM THE
 FEE OWNER ACKNOWLEDGING THE DECISION TO USE PRIVATE
 PROVIDERS UNDER FS 533.791(4)(C). NO SUCH INFORMATION
 COULD BE FOUND IN THE PACKAGE SUBMITTED FOR PERMIT.
 PROVIDE ALL REQUIRED DOCUMENTATION PURSUANT TO THIS
 STATUTE.
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH A
 DESCRIPTION OF HOW THE COMMENT HAS BEEN ADDRESSED (OR
 WHY IT HAS NOT) AS WELL AS WHERE THE RELEVANT
 INFORMATION CAN BE FOUND. ALSO, PLEASE RETURN ONE SET
 OF OLD/VOIDED PLANS FOR REFERENCE. THESE STEPS WILL
 HELP TO ENSURE A TIMELY REVIEW UPON RESUBMISSION.
  