Date |
Text |
2008-02-14 15:57:29 | *****DENIED***** |
| |
| |
| 01.THE ASSIGNED SUITE NUMBER SHALL BE INCLUDED IN THE |
| ADDRESS LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED |
| PLAN SHEET. |
| |
| 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 03.IN ADDITION TO THE 2004 FLORIDA FIRE PREVENTION |
| CODE AS LISTED IN THE CODE NOTES ON SHEET G0201, NFPA |
| 101- LIFE SAFETY CODE - 2003 EDITION SHALL BE |
| REFERENCED. |
| |
| 04.NO EXIT LIGHTS/DOORS SHOWN ON LIFE SAFETY PLAN |
| (SHEET A0001) TO DETERMINE IF THE PATH OF TRAVEL IS TO |
| THE EXIT(S). |
| |
| 05.ON SHEET A0401,EXIT LIGHTS DIRECT PERSON(S) TO |
| THE CORRIDORS.WHERE DO PERSON(S) GO ONCE THEY'RE IN |
| THE CORRIDOR?CORRELATE THIS SHEET WITH G0201, E200 |
| |
| 06.GENERAL SHEET NOTE # 5 INCOMPLETE AS SHOWN ON |
| SHEETS A0501 AND A0502. |
| |
| 07.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO |
| THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON |
| THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS |
| SHALL BE NO LESS THAN 3" IN HEIGHT. |
| |
| 08.DOOR(S) LEADING DIRECTLY TO THE CORRIDOR SHALL BE |
| AN APPROVED, LISTED, AND LABELED FIRE DOOR & ASSEMBLY |
| IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 80. |
| |
| 09.SPECIFY THE INTERIOR FINISH CLASSIFICATION FOR THE |
| WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR |
| CLASS C. |
| |
| 10.PLEASE CLARIFY OR CORRELATE THE NUMBER OF CORRIDOR |
| EMERGENCY LIGHTING FIXTURES.ON SHEET E200 AND SHEET |
| E201 THER ARE15 DEVICES SHOWN, BUT 30 DEVICES ARE |
| LISTED IN THE DESIGN CRITERIA LUMINAIRES USED |
| INFORMATION DATA ON SHEET E201. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS |
| ADDRESSED |
| |
| |