Plan Review Notes
Plan Review Notes For Permit 08020160
Permit Number 08020160
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-11 10:40:15 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE REQUIRED AFFIDAVIT AS REQUIRED
 PER FS 553.791(4)(C) WAS NOT SUBMITTED.
  
 2) NOTE: PLEASE SEE THE PLANS NEED TO CONTAIN THE
 FOLLOWING RELEVANT CODES STATED FOR DESIGN.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** SOME MAY ALREADY BE SHOWN HOWEVER NOT ALL. PLEASE BE
 AWARE OF ANY CODES REQUIRED BY OTHER TRADE REVIEWERS.
 PLEASE ALSO SEE THE CODES ARE NEEDED ON ELECTRICAL AS
 WELL.
 FBC 106.5, 106.1.2, FS 553.73
  
 3) NOTE: PLEASE SEE THAT THE SUITE/UNIT NUMBER IS
 REFLECTED ON TITLE BLOCKS. PLEASE KNOW IF ANY
 PARTICULAR SHEET DOES NOT NEED TO BE REVISED FOR CODE
 COMPLIANCE, THEN THIS MAY BE HAND PRINTED ON SHEETS.
 FBC 106.1.2, 106.5
 FAC 61G1-16.004, FAC 61G15-23.002
  
 4) NOTE: PLEASE SEE MISSING LICENSE INFORMATION ON
 TITLE BLOCKS FOR URS CORPORATION. PLEASE SEE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER FOR ARCHITECTURAL
 FIRM WHICH IS REQUIRED PER FS 481.219 AND TO BE ON
 PLANS PER FAC 61G1-16.004
 PLEASE ALSO SEE FS 471.023 AND FAC 61G15-23.002 WHICH
 REQUIRES CERTIFICATE OF AUTHORIZATION NUMBER FOR
 ENGINEERING BUSINESS AS WELL.
  
 5) NOTE: PLEASE PLACE NOTES ON PLANS FOR REQUIRED
 GROUNDING AND INSTALLATION OF SYSTEMS PER NEC 517.
 PLEASE SEE 517.1 COMMENTARIES WHICH ARE QUOTED BELOW:
  
 *THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY
 TO ALL TYPES OF HEALTH CARE FACILITIES. THE
 REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE
 NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC
 MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES
 WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE
 WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE
 REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER
 PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS
 ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE
 REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45
 IN ARTICLE 517.*
 PLEASE ALSO BE AWARE ANY UNDER GROUND SLAB AREAS TO
 EQUIPMENT SHALL BE RMC, IMC OR OTHER APPROVED CONDUIT
 SYSTEM. 517.13, 250, AND SEE USES PERMITTED IN CHAPTER
 13 FOR CONDUITS.
  
 6) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND NOTES
 ON PLANS ACCORDINGLY.
  
 7) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 A LIGHTING CONTROL SYSTEM IS BEING NOTED HOWEVER OVER
 RIDES AND LOCATIONS ARE IN NEED OF MEETING THE ABOVE
 SECTIONS. MANY OF THESE ARE SHOWN AS STANDARD SWITCHES.
 SOME AREAS ARE EXEMPT PER EXCEPTIONS LISTED IN
 13-415.1.ABC.1.1
 PLEASE LIST SCHEDULING.
 PLEASE LIST MAXIMUM TIMES ON OVER RIDES.
 PLEASE SUBMIT DETAIL FOR ANY LIGHTING WHICH IS BEING
 OVER RIDDEN FROM A LOCATION IN WHICH THE LIGHTING BEING
 CONTROLLED CAN NOT BEE SEEN.
 PLEASE KNOW AT THIS TIME THERE ARE SEVERAL ITEMS WHICH
 CAN NOT BE REVIEWED AND MAY HAVE NEW COMMENTS WHICH CAN
 NOT BE MADE AT THIS TIME.
  
 8) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2.
  
 9) NOTE: PLEASE SEE ROOM 14-312 WHICH INDICATES *FAN
 ROOM* PLEASE INDICATE AS DEDICATED ELECTRICAL
 /MECHANICAL SPACE.
 110.26
  
 10) NOTE: PLEASE CLARIFY THE ITD ROOM # 14-121 ON
 PLANS. ARCHITECTURAL SHEETS INDICATE 1HR FIRE RATING
 AND THIS ROOM CONTAINS SEPARATE A/C SYSTEM HOWEVER
 COULD NOT LOCATE THE REQUIRED DISCONNECTING MEANS PER
 645.10 FOR ALL. PLANS CONTAIN NOTE FOR MOST RECEPTACLES
 HOWEVER SOME ARE FED FROM A SEPARATE PANEL ALL
 TOGETHER. PLEASE CLARIFY USE OF THESE.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 NEW PROPOSED IT EQUIPMENT.
 110.3, 90.7. PLEASE BE SURE SPECS/CUT SHEETS INDICATE A
 LISTING FROM A NRTL. (NATIONALLY RECOGNIZED TESTING
 LABORATORY).
  
 11) NOTE: PLEASE SEE THE TAPPED CONDUCTORS ON THE
 SECONDARY SIDE OF TRANSFORMER T112.5 ARE REQUIRED TO BE
 RATED FOR THE OVER CURRENT PROTECTION IN WHICH ARE
 BEING TERMINATED. PLEASE SEE 240.21, 310.16, 240.4 AND
 110.14.
 PLEASE KNOW IT IS ACCEPTABLE TO MOVE TO THE NEXT SIZE
 BREAKER (DEVICES 800AMPS AND LOWER) ON TYPICAL FEEDERS
 ETC HOWEVER NOT ON THE SECONDARY SIDE OF THE
 TRANSFORMER.
 THIS WAS INFORMATION GIVEN AND CONFIRMED BY THE CODE
 PANELIST AND NFPA.
 PLEASE ADJUST THESE TAPPED CONDUCTORS.
  
 12) NOTE: PLEASE PROVIDE GROUNDING ELECTRODE ATTACHMENT
 POINT FOR THE TRANSFORMER GROUNDING PER 250.30, 250.50,
 AND 250.66.
  
 13) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON EXISTING
 EL41A FOR NEW LOAD BEING ADDED TO EXISTING SYSTEM
 SERVICE EQUIPMENT.
 220.87.
  
 14) NOTE: PLEASE KNOW THE NEW ELECTRIC WATER HEATER IS
 REQUIRED TO BE FIGURED INTO ENERGY CONSUMPTION. PLEASE
 SEE 13-412.1.ABC.3.4
  
 15) NOTE: PLEASE INDICATE ALL MINIMUM LEVELS FOR
 SOUNDING DEVICES PER FBC 11-4.28.1, .2. PLEASE SEE
 VISUAL DEVICES APPEAR TO BE OK ATTHIS TIME FOR ADA
 COMPLIANCE.
 PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM FIRE
 MARSHAL WHICH MAY AFFECT THE ELECTRICAL AND/OR F
 SHEETS.
  
 16) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS PER
 13-413.1.ABC.1.1. PLEASE SEE MORE SPECIFICALLY THE
 FEEDERS FROM 4TH FLOOR TO ECB.
  
 17) NOTE: PLEASE PROVIDE MORE INFORMATION PER
 517.71-517.78.
 SOME ITEMS ARE SHOWN HOWEVER NOT ALL.
  
 18) NOTE: PLEASE KNOW THESE PLANS MAY BE REFERENCED FOR
 LOW VOLTAGE SCOPE OF WORK HOWEVER THE LV WILL BE
 REQUIRED TO BE UNDER SEPARATE PERMIT. THIS IS NOTED FOR
 INFORMATION ONLY AT THIS TIME.
  
 ** PLEASE KNOW AS THERE ARE ITEMS NOT YET SUBMITTED
 THERE MAY BE COMMENTS WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION. IF THERE ARE ANY
 QUESTIONS PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE/REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved