Date |
Text |
2008-02-11 10:40:15 | |
| ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE SEE THE REQUIRED AFFIDAVIT AS REQUIRED |
| PER FS 553.791(4)(C) WAS NOT SUBMITTED. |
| |
| 2) NOTE: PLEASE SEE THE PLANS NEED TO CONTAIN THE |
| FOLLOWING RELEVANT CODES STATED FOR DESIGN. |
| 2004 FBC W/2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| ** SOME MAY ALREADY BE SHOWN HOWEVER NOT ALL. PLEASE BE |
| AWARE OF ANY CODES REQUIRED BY OTHER TRADE REVIEWERS. |
| PLEASE ALSO SEE THE CODES ARE NEEDED ON ELECTRICAL AS |
| WELL. |
| FBC 106.5, 106.1.2, FS 553.73 |
| |
| 3) NOTE: PLEASE SEE THAT THE SUITE/UNIT NUMBER IS |
| REFLECTED ON TITLE BLOCKS. PLEASE KNOW IF ANY |
| PARTICULAR SHEET DOES NOT NEED TO BE REVISED FOR CODE |
| COMPLIANCE, THEN THIS MAY BE HAND PRINTED ON SHEETS. |
| FBC 106.1.2, 106.5 |
| FAC 61G1-16.004, FAC 61G15-23.002 |
| |
| 4) NOTE: PLEASE SEE MISSING LICENSE INFORMATION ON |
| TITLE BLOCKS FOR URS CORPORATION. PLEASE SEE MISSING |
| CERTIFICATE OF AUTHORIZATION NUMBER FOR ARCHITECTURAL |
| FIRM WHICH IS REQUIRED PER FS 481.219 AND TO BE ON |
| PLANS PER FAC 61G1-16.004 |
| PLEASE ALSO SEE FS 471.023 AND FAC 61G15-23.002 WHICH |
| REQUIRES CERTIFICATE OF AUTHORIZATION NUMBER FOR |
| ENGINEERING BUSINESS AS WELL. |
| |
| 5) NOTE: PLEASE PLACE NOTES ON PLANS FOR REQUIRED |
| GROUNDING AND INSTALLATION OF SYSTEMS PER NEC 517. |
| PLEASE SEE 517.1 COMMENTARIES WHICH ARE QUOTED BELOW: |
| |
| *THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY |
| TO ALL TYPES OF HEALTH CARE FACILITIES. THE |
| REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE |
| NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC |
| MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES |
| WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE |
| WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE |
| REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER |
| PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS |
| ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE |
| REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45 |
| IN ARTICLE 517.* |
| PLEASE ALSO BE AWARE ANY UNDER GROUND SLAB AREAS TO |
| EQUIPMENT SHALL BE RMC, IMC OR OTHER APPROVED CONDUIT |
| SYSTEM. 517.13, 250, AND SEE USES PERMITTED IN CHAPTER |
| 13 FOR CONDUITS. |
| |
| 6) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND NOTES |
| ON PLANS ACCORDINGLY. |
| |
| 7) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| A LIGHTING CONTROL SYSTEM IS BEING NOTED HOWEVER OVER |
| RIDES AND LOCATIONS ARE IN NEED OF MEETING THE ABOVE |
| SECTIONS. MANY OF THESE ARE SHOWN AS STANDARD SWITCHES. |
| SOME AREAS ARE EXEMPT PER EXCEPTIONS LISTED IN |
| 13-415.1.ABC.1.1 |
| PLEASE LIST SCHEDULING. |
| PLEASE LIST MAXIMUM TIMES ON OVER RIDES. |
| PLEASE SUBMIT DETAIL FOR ANY LIGHTING WHICH IS BEING |
| OVER RIDDEN FROM A LOCATION IN WHICH THE LIGHTING BEING |
| CONTROLLED CAN NOT BEE SEEN. |
| PLEASE KNOW AT THIS TIME THERE ARE SEVERAL ITEMS WHICH |
| CAN NOT BE REVIEWED AND MAY HAVE NEW COMMENTS WHICH CAN |
| NOT BE MADE AT THIS TIME. |
| |
| 8) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE |
| CALCULATIONS PER 13-415.2. |
| |
| 9) NOTE: PLEASE SEE ROOM 14-312 WHICH INDICATES *FAN |
| ROOM* PLEASE INDICATE AS DEDICATED ELECTRICAL |
| /MECHANICAL SPACE. |
| 110.26 |
| |
| 10) NOTE: PLEASE CLARIFY THE ITD ROOM # 14-121 ON |
| PLANS. ARCHITECTURAL SHEETS INDICATE 1HR FIRE RATING |
| AND THIS ROOM CONTAINS SEPARATE A/C SYSTEM HOWEVER |
| COULD NOT LOCATE THE REQUIRED DISCONNECTING MEANS PER |
| 645.10 FOR ALL. PLANS CONTAIN NOTE FOR MOST RECEPTACLES |
| HOWEVER SOME ARE FED FROM A SEPARATE PANEL ALL |
| TOGETHER. PLEASE CLARIFY USE OF THESE. |
| PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE |
| NEW PROPOSED IT EQUIPMENT. |
| 110.3, 90.7. PLEASE BE SURE SPECS/CUT SHEETS INDICATE A |
| LISTING FROM A NRTL. (NATIONALLY RECOGNIZED TESTING |
| LABORATORY). |
| |
| 11) NOTE: PLEASE SEE THE TAPPED CONDUCTORS ON THE |
| SECONDARY SIDE OF TRANSFORMER T112.5 ARE REQUIRED TO BE |
| RATED FOR THE OVER CURRENT PROTECTION IN WHICH ARE |
| BEING TERMINATED. PLEASE SEE 240.21, 310.16, 240.4 AND |
| 110.14. |
| PLEASE KNOW IT IS ACCEPTABLE TO MOVE TO THE NEXT SIZE |
| BREAKER (DEVICES 800AMPS AND LOWER) ON TYPICAL FEEDERS |
| ETC HOWEVER NOT ON THE SECONDARY SIDE OF THE |
| TRANSFORMER. |
| THIS WAS INFORMATION GIVEN AND CONFIRMED BY THE CODE |
| PANELIST AND NFPA. |
| PLEASE ADJUST THESE TAPPED CONDUCTORS. |
| |
| 12) NOTE: PLEASE PROVIDE GROUNDING ELECTRODE ATTACHMENT |
| POINT FOR THE TRANSFORMER GROUNDING PER 250.30, 250.50, |
| AND 250.66. |
| |
| 13) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON EXISTING |
| EL41A FOR NEW LOAD BEING ADDED TO EXISTING SYSTEM |
| SERVICE EQUIPMENT. |
| 220.87. |
| |
| 14) NOTE: PLEASE KNOW THE NEW ELECTRIC WATER HEATER IS |
| REQUIRED TO BE FIGURED INTO ENERGY CONSUMPTION. PLEASE |
| SEE 13-412.1.ABC.3.4 |
| |
| 15) NOTE: PLEASE INDICATE ALL MINIMUM LEVELS FOR |
| SOUNDING DEVICES PER FBC 11-4.28.1, .2. PLEASE SEE |
| VISUAL DEVICES APPEAR TO BE OK ATTHIS TIME FOR ADA |
| COMPLIANCE. |
| PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM FIRE |
| MARSHAL WHICH MAY AFFECT THE ELECTRICAL AND/OR F |
| SHEETS. |
| |
| 16) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS PER |
| 13-413.1.ABC.1.1. PLEASE SEE MORE SPECIFICALLY THE |
| FEEDERS FROM 4TH FLOOR TO ECB. |
| |
| 17) NOTE: PLEASE PROVIDE MORE INFORMATION PER |
| 517.71-517.78. |
| SOME ITEMS ARE SHOWN HOWEVER NOT ALL. |
| |
| 18) NOTE: PLEASE KNOW THESE PLANS MAY BE REFERENCED FOR |
| LOW VOLTAGE SCOPE OF WORK HOWEVER THE LV WILL BE |
| REQUIRED TO BE UNDER SEPARATE PERMIT. THIS IS NOTED FOR |
| INFORMATION ONLY AT THIS TIME. |
| |
| ** PLEASE KNOW AS THERE ARE ITEMS NOT YET SUBMITTED |
| THERE MAY BE COMMENTS WHICH CAN NOT BE MADE AT THIS |
| TIME. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION. IF THERE ARE ANY |
| QUESTIONS PLEASE DO NOT HESITATE IN CONTACTING THIS |
| OFFICE/REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |