Plan Review Notes
Plan Review Notes For Permit 08020154
Permit Number 08020154
Review Stop G
Sequence Number 1
Notes
Date Text
2008-02-27 16:31:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 **THE SUBMITTED ISOMETRIC GAS RISER DOES NOT INDICATE
 THE CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 THE ONLY DEMENTIONS BEING INDICATED ARE 50' TOTAL
 DEVELOPED LENGTH. DOES THAT INCLUDE THE EXISTING GAS?
 GAS PLAN REVIEW NEEDS TO HAVE EACH CUT SECTION OF PIPE
 FOR THE PROPOSED GENERATOR INDICATED AS WELL AS THE
 LONGEST LENGTH OF THE EXISTING SYSTEM.
  
 2. CLEARLY INDICATE THETYPE OF GAS, (LP OR NATURAL)
 BEING USED. PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **THIS INCLUDES THE EXISTING BTU LOADS TO THE HOUSE AS
 WELL AS THE PROPOSED BTU LOAD OF THE GENERATOR. A GAS
 PLAN REVIEW CAN NOT BE DONE WITHOUT A TOTAL BTU LOAD OF
 THE SYSTEM BEING KNOWN.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **THIS INCLUDES THE EXISTING SYSTEM DISTANCE TO THE
 HOUSE AS WELL AS THE PROPOSED GENERATOR'S DISTANCE. GAS
 PLAN REVIEW CAN NOT BE DONE WITHOUT KNOWING THE LONGEST
 LENGTH OF THE SYSTEM
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 **A GAS PLAN REVIEW CAN NOT BE DONE WITHOUT KNOWING
 THE PRESSURE TO THE SYSTEM.
  
 6. REFERENCE MECHANICAL COMMENT #1 AND COMPLY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved