Date |
Text |
2008-02-27 16:31:04 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| GAS PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE SECTION 401.1 SCOPE. |
| **THE SUBMITTED ISOMETRIC GAS RISER DOES NOT INDICATE |
| THE CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. |
| THE ONLY DEMENTIONS BEING INDICATED ARE 50' TOTAL |
| DEVELOPED LENGTH. DOES THAT INCLUDE THE EXISTING GAS? |
| GAS PLAN REVIEW NEEDS TO HAVE EACH CUT SECTION OF PIPE |
| FOR THE PROPOSED GENERATOR INDICATED AS WELL AS THE |
| LONGEST LENGTH OF THE EXISTING SYSTEM. |
| |
| 2. CLEARLY INDICATE THETYPE OF GAS, (LP OR NATURAL) |
| BEING USED. PER FBC FUEL GAS SECTION 401.1 SCOPE. |
| |
| 3. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| **THIS INCLUDES THE EXISTING BTU LOADS TO THE HOUSE AS |
| WELL AS THE PROPOSED BTU LOAD OF THE GENERATOR. A GAS |
| PLAN REVIEW CAN NOT BE DONE WITHOUT A TOTAL BTU LOAD OF |
| THE SYSTEM BEING KNOWN. |
| |
| 4. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| **THIS INCLUDES THE EXISTING SYSTEM DISTANCE TO THE |
| HOUSE AS WELL AS THE PROPOSED GENERATOR'S DISTANCE. GAS |
| PLAN REVIEW CAN NOT BE DONE WITHOUT KNOWING THE LONGEST |
| LENGTH OF THE SYSTEM |
| |
| 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| **A GAS PLAN REVIEW CAN NOT BE DONE WITHOUT KNOWING |
| THE PRESSURE TO THE SYSTEM. |
| |
| 6. REFERENCE MECHANICAL COMMENT #1 AND COMPLY. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |