Plan Review Notes For Permit 08020152 |
Permit Number |
08020152 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-02-08 15:37:57 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | AMENDED. | | | | A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED | | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. | | 108.1 FBC. | | | | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY | | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|