Plan Review Notes
Plan Review Notes For Permit 08020096
Permit Number 08020096
Review Stop B
Sequence Number 1
Notes
Date Text
2008-02-13 14:32:57PORCH W/ INSULATED ROOF, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE 2 COPIES OF PRODUCT APPROVAL FOR INSULATED
 ROOF PANELS AS REQUIRED BY DCA RULE 9B-72.
  
 2- DESIGNER OF RECORD TO REVIEW AN APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 ***NOTE:REFER TO ROOF PANELS PRODUCT APPROVAL TO MAKE
 SURE CONNECTION INSTALLATIONS ARE COORDINATED WITH
 ENGINEER'S GENERAL DETAILS TO AVOID CONFLICTS OR
 DELAYS.
  
 3- OWES $3.60 FOR RADON FEES.
  
 4- ENGINEER TO REVISE DESIGN CRITERIA ON SHEET 1 OF 1:
  
 A) REFERENCE CURRENT FBC 2004REVISIONS.REFERENCE
 2007 REVISIONS, NOT 2006.
  
 B) THIS STRUCTURE CAN NOT BE DESIGNED AS AN OPEN
 STRUCTURE. SEEDEFINITIONS ON SEC. 1609.2 OF FBC 2004
 AND REVISE ALL DESIGN CRITERIA AS REQUIRED.
  
 C) ENGINEER TO SPECIFY ALL LOADS AS REQUIRED BY SEC.
 1607.11 FBC 2004.
  
 5- GENERAL DETAILS SHEETS:
 A) ENGINEER TO CLEARLY MARK ALL THE SPECIFIC
 DETAILS,INCLUDING GUTTERS,AND COLUMN AND BEAM
 TABLES THAT APPLY TO THIS SITE SPECIFIC JOB. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: TAKE INTO CONSIDERATION THAT TABLES AND
 DETAILS NEED TO COMPLY WITHSTRUCTURE TYPE. SEE ITEM
 4(B) ABOVE.
  
 B) ENGINEER TO SPECIFY WHERE ARE THE COLUMN AND BEAM
 TABLES TAKEN FROM.AND, MAKE SURE TABLES INCLUDE SIZE
 OF COLUMNS AND BEAMS SPECIFIED ON SHEET 1 OF 1. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) REVISE GENERAL NOTES REGARDING THE IMPORTANCE
 FACTOR. SEE ITEM4(C)ABOVE.
 ALSO, REVISE AMENDMENTS REFERENCE. REFER TO 2007
 REVISIONS, NOT 2006.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712