2008-02-06 14:19:10 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.ENHANCED FASTENING NOT COMPLIANT FOR ZONE 3. | | FASTENER VALUE IS TO BE LESS THAN 38.69; FASTENER VALUE | | FOR SPACING SPECIFIED (4" LAPS, 9" FIELD ROWS) IS | | 46.29. | | | | 2.THE WEATHERGUARD PRODUCT APPROVAL STATES THAT IT IS | | FOR USE ON SLOPED ASSEMBLIES.PLEASE PROVIDE | | DOCUMENTATION SHOWING THAT IT IS ACCEPTABLE FOR USE ON | | A FLAT DECK. | | | | 3.ALTERNATELY, AN APPROVED MODIFIED SHEET CAN BE USED | | AS AN OPTIONAL PLY SHEET WITHIN THE ROOF ASSEMBLY. | | PLEASE CONTACT ME IF YOU NEED FURTHER INFORMATION. | | |
|