Plan Review Notes
Plan Review Notes For Permit 08020090
Permit Number 08020090
Review Stop B
Sequence Number 1
Notes
Date Text
2008-02-06 14:19:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.ENHANCED FASTENING NOT COMPLIANT FOR ZONE 3.
 FASTENER VALUE IS TO BE LESS THAN 38.69; FASTENER VALUE
 FOR SPACING SPECIFIED (4" LAPS, 9" FIELD ROWS) IS
 46.29.
  
 2.THE WEATHERGUARD PRODUCT APPROVAL STATES THAT IT IS
 FOR USE ON SLOPED ASSEMBLIES.PLEASE PROVIDE
 DOCUMENTATION SHOWING THAT IT IS ACCEPTABLE FOR USE ON
 A FLAT DECK.
  
 3.ALTERNATELY, AN APPROVED MODIFIED SHEET CAN BE USED
 AS AN OPTIONAL PLY SHEET WITHIN THE ROOF ASSEMBLY.
 PLEASE CONTACT ME IF YOU NEED FURTHER INFORMATION.
  