Plan Review Notes
Plan Review Notes For Permit 08020067
Permit Number 08020067
Review Stop B
Sequence Number 6
Notes
Date Text
2010-01-20 12:00:152004 FBC W/2007 REVISIONS
 APPLICATION FOR SUCCESSOR ARCHITECT
  
 DENIED BY BUILDING
  
 1) TWO SETS OF PLANS, WHICH ARE COPIES OF THE APPROVED
 PLANS WITH THE TITLE BLOCKS CHANGED TO A DIFFERENT
 DESIGNER OF RECORD (ARCHITECT) WERE SUBMITTED. THE
 INTENT OF THE NEW ARCHITECT IS TO ADOPT THE WORK OF THE
 ORIGNIAL DESIGNER OF RECORD AS ALLOWED BY FAC
 61G1-18.002. THE SIGNED AND SEALED LETTER FROM THE
 SUCCESSOR ARCHITECT STATES THAT A NOTIFICATION LETTER
 WAS SENT TO THE GARRISON DESIGN GROUP. THE DESIGNER OF
 RECORD IS THE ENGINEER THAT SIGNED AND SEALED THE
 ORIGINAL PLANS, LUIS A. LOPEZ, PE # 59805. IN
 ACCORDANCE WITH FAC 61G15-27.001 AND FAC 61G1-18.002
 THE ORIGINAL ENGINEER IS REQUIRED TO BE NOTIFIED BY
 CERTIFIED LETTER OF THE SUCCESSOR'S INTENTION TO USE
 THE ORIGINAL PROFESSIONAL ENGINEER'S WORK. THE
 SUCCESSOR ARCHITECT OR ENGINEER MUST BE ABLE TO
 DOCUMENT AND PRODUCE UPON REQUEST EVIDENCE THAT HE HAS
 IN FACT RECREATED ALL THE WORK DONE BY THE ORIGINAL
 PROFESSIONAL ENGINEER. FURTHER THE SUCESSOR MUST TAKE
 ALL PROFESSIONAL AND LEGAL RESPONSIBLITY FOR THE
 DOCUMENTS WHICH HE SEALED AND SIGNED AND CAN IN NO WAY
 EXEMPT HIMSELF FROM SUCH FULL RESPONSIBILITY.
  
 PLEASE SUBMIT TWO NEW LETTERS WHICH INDICATE THAT THE
 ABOVE REQUIREMENTS HAVE BEEN MET AND THAT DOCUMENTATION
 CAN BE PROVIDED UPON REQUEST.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]