Plan Review Notes For Permit 08020067
Permit Number 08020067
Review Stop M
Sequence Number 3
Notes
Date Text
2008-12-07 14:44:34REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: MECHANICAL PLANS HAVE NOW BEEN SUBMITTED FOR
 REVIEW FOR THE FIRST TIME. ALL PREVIOUS REVIEW COMMENTS
 HAVE BEEN ADDRESSED. PLEASE ADDRESS THE FOLLOWING
 RELATED TO NEW MECHANICAL PLANS:
  
 1. THE GUEST AREA AND 2ND FLOOR, ALL DUCTS ARE MISSING
 SIZES. PLEASE SHOW THE SIZE OF ALL AIR DISTRIBUTION
 COMPONENTS TO BE INSTALLED IN ORDER TO DEMONSTRATE
 COMPLIANCE WITH FBCR M1601.1 AND M1601.3 AS WELL AS
 M1602.4 FOR BALANCED RETURN AIR.
  