2008-12-03 13:18:34 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| COMMENTS FOR SHEETE2. |
| |
| 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| |
| 2} LOCATE ALL SERVICE EQUIPMENT ON THE RISER DIAGRAM. |
| IF PANEL "B" IS THE GUEST HOUSE PANEL IT MUST HAVE A |
| MAIN BREAKER OR A DISCONNECT PER 225.31, LOCATED PER |
| 225.32 AND GROUNDED PER 250.32. |
| |
| 3} THE WASHER /LAUNDRY CIRCUIT IS NOT LISTED ON THE |
| PANEL SCHEDULE. 210.11(C)(2). |
| |
| 4} THERE ARE TWO GUEST HOUSE WATER HEATERS LISTED IN |
| PANEL "B", BUT ONLY ONE SHOWN ON THE FLOOR PLAN, |
| CORRELATE SAME.VERIFY THE MAIN HOUSE WATER HEATER IS |
| FED FROM PANEL "B", IF IN FACT PANEL "B" IS LOCATED IN |
| THE GUEST HOUSE. |
| |
| 5} A SERVICE RECEPTACLE PER 210.63 IS REQUIRED FOR THE |
| ACU FOR THE GUEST HOUSE. |
| |
| 6} THE LOAD CALCULATION LISTS ALL HEAT STRIPS AT 10000W |
| WHICH DOES NOT CORRELATE WITH THE PANEL SCHEDULE OR |
| MANUFACTURERS SPEC'S ON M1. |
| |
| 7} A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR |
| SHOWN ON THE RISER DIAGRAM UNLESS ALL DOCUMENTS |
| REQUIRED FOR A RESIDENTIAL GENERATOR ARE SUBMITTED WITH |
| THIS APPLICATION. |
| |