Plan Review Notes
Plan Review Notes For Permit 08020067
Permit Number 08020067
Review Stop E
Sequence Number 3
Notes
Date Text
2008-12-03 13:18:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 COMMENTS FOR SHEETE2.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} LOCATE ALL SERVICE EQUIPMENT ON THE RISER DIAGRAM.
 IF PANEL "B" IS THE GUEST HOUSE PANEL IT MUST HAVE A
 MAIN BREAKER OR A DISCONNECT PER 225.31, LOCATED PER
 225.32 AND GROUNDED PER 250.32.
  
 3} THE WASHER /LAUNDRY CIRCUIT IS NOT LISTED ON THE
 PANEL SCHEDULE. 210.11(C)(2).
  
 4} THERE ARE TWO GUEST HOUSE WATER HEATERS LISTED IN
 PANEL "B", BUT ONLY ONE SHOWN ON THE FLOOR PLAN,
 CORRELATE SAME.VERIFY THE MAIN HOUSE WATER HEATER IS
 FED FROM PANEL "B", IF IN FACT PANEL "B" IS LOCATED IN
 THE GUEST HOUSE.
  
 5} A SERVICE RECEPTACLE PER 210.63 IS REQUIRED FOR THE
 ACU FOR THE GUEST HOUSE.
  
 6} THE LOAD CALCULATION LISTS ALL HEAT STRIPS AT 10000W
 WHICH DOES NOT CORRELATE WITH THE PANEL SCHEDULE OR
 MANUFACTURERS SPEC'S ON M1.
  
 7} A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR
 SHOWN ON THE RISER DIAGRAM UNLESS ALL DOCUMENTS
 REQUIRED FOR A RESIDENTIAL GENERATOR ARE SUBMITTED WITH
 THIS APPLICATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676
  