Plan Review Notes
Plan Review Notes For Permit 08020067
Permit Number 08020067
Review Stop M
Sequence Number 2
Notes
Date Text
2008-08-04 16:32:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 THE FOLLOWING NOTES ARE FROM THE LAST REVIEW 2-7-08
 THAT WERE NOT CORRECTED.
  
 1) THE MAIN HOUSE AND THE GUEST HOUSE CAN NOT BE ON THE
 SAME ENERGY CALCULATION. PLEASE SUBMIT SEPARATE ENERGY
 CALCULATIONS FOR EACH BUILDING, SEE 2004 FBC
 13-101.2.5.1. (THE OLD ENERGY CALCULATIONS WERE
 RESUBMITTED NOT REVISED ONES).
  
 2) PLEASE HAVE THE REVISED ENERGY CALCULATIONS SIGNED
 BY OWNER/AGENT ALSO, SEE 2004 FBC 13-600.3.ABC.2. (SEE
 RESPONSE ABOVE #1).
  
 3) ENERGY CALCULATIONS LINE 8B DOES NOT SHOW THE RAISED
 WOOD FLOOR OR INSULATION, SEE 2004 FBC 13-605.2.A.1.1
 AND 13-605.1.C.2. PLEASE CORRECT ALSO THE PLANS IF
 NEEDED. (SEE RESPONSE ABOVE #1).
  
 4) SHOW AN A/C EQUIPMENT SCHEDULE WITH ALL THE
 PERTINENT INFORMATION ON THE MECHANICAL PLAN, SEE 2004
 WPB AMEND. 106.3.5.4 (10). (NO MECHANICAL PLANS WERE
 SUBMITTED FOR REVIEW).
  
 5) SHOW ALL THE BATHROOM EXHAUST FANS ON THE MECHANICAL
 PLAN AS THEY ARE ON THE ELECTRICAL PLAN, SEE 2004 FBC/R
 R303.3 EXCEPT. (SEE RESPONSE ABOVE #4).
  
 6) SHOW THE LOCATION OF THE GUEST HOUSE A/C CONDENSER
 UNIT ON THE MECHANICAL AND ELECTRICAL PLANS, SEE 2004
 FBC/R M1307. (SEE RESPONSE ABOVE #4).
  
 7) A/C SYSTEM 2 COOLING LOAD CALCULATIONS ARE CALLING
 FOR 23,601 TOTAL COOLING BTU'S. A 3 TON A/C SYSTEM AT
 34,200 TOTAL COOLING BTU'S WOULD BE TO LARGE AS YOU CAN
 ONLY GO 15% OVER THE COOLING LOAD CALCULATION, SEE 2004
 FBC 13-607.1.ABC.1.1. PLEASE CORRECT. (REVISED COOLING
 LOAD CALCULATIONS WERE SUBMITTED BUT NO MECHANICAL
 PLANS WERE SUBMITTED).
  
 8) A/C SYSTEM 3 COOLING LOAD CALCULATIONS ARE CALLING
 FOR 23,046 TOTAL COOLING BTU'S. A 3 TON A/C SYSTEM AT
 34,200 TOTAL COOLING BTU'S WOULD BE TO LARGE AS YOU CAN
 ONLY GO 15% OVER THE COOLING LOAD CALCULATION, SEE 2004
 FBC 13-607.1.ABC.1.1. PLEASE CORRECT. (SEE RESPONSE
 ABOVE #7).
  
 9) ELECTRICAL PLAN E-2 IS SHOWING A GAS INSTA-HOT WATER
 HEATER IN THE GARAGE OF THE GUEST HOUSE, THIS MAY BE A
 CONFINED SPACE. PLEASE SUBMIT COMBUSTION AIR
 CALCULATIONS, SEE 2004 FBC/R G2407.5. (THE GAS
 APPLIANCE MAY BE INSTALLED UNDER A SEPARATE PERMIT BUT
 THE SPACE THE GAS APPLIANCE IS BEING INSTALLED IN IS
 PART OF THIS PERMIT, PLEASE COMPLY).
  
 10) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S FOR
 THE GAS INSTA-HOT WATER HEATER AND GAS WATER HEATER
 BEING INSTALLED IN MAIN HOUSE, PER 2004 FBC/R G2407.1.
 (SEE RESPONSE ABOVE #9).
  
 11) NEW NOTE: PLANS SHOW A GAS WATER HEATER BEING
 INSTALLED IN A CLOSET OF THE MAIN HOUSE FIRST FLOOR.
 THIS MAY BE A CONFINED SPACE, PLEASE SUBMIT COMBUSTION
 AIR CALCULATIONS, PER 2004 FBC/R G2407.5.
  
 12) NOTICE: SEE ATTACHED NOTICE FS 553.80 (2) (B)
 REGARDING FOUR TIMES THE FEE.
  
 *** 2004 FBC/R G2407.1 (304.1) GENERAL.
 AIR FOR COMBUSTION, VENTILATION AND DILUTION OF FLUE
 GASES FOR GAS UTILIZATION EQUIPMENT INSTALLED IN
 BUILDINGS SHALL BE PROVIDED BY APPLICATION OF ONE OF
 THE METHODS PRESCRIBED IN SECTIONS G2407.5 THROUGH
 G2407.9 . WHERE THE REQUIREMENTS OF SECTION G2407.5 ARE
 NOT MET, OUTDOOR AIR SHALL BE INTRODUCED IN ACCORDANCE
 WITH ONE OF THE METHODS PRESCRIBED IN SECTIONS G2407.6
 THROUGH G2407.9 . DIRECT-VENT APPLIANCES, GAS
 APPLIANCES OF OTHER THAN NATURAL DRAFT DESIGN AND
 VENTED GAS APPLIANCES OTHER THAN CATEGORY I SHALL BE
 PROVIDED WITH COMBUSTION, VENTILATION AND DILUTION AIR
 IN ACCORDANCE WITH THE EQUIPMENT MANUFACTURER?S
 INSTRUCTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]