Plan Review Notes For Permit 08020067 |
Permit Number |
08020067 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-02-08 08:34:40 | DENIED; | | 1. ADDRESS OF JOB ISREQUIRED ON ALLPAGES OF | | PLANS.FBC BUILDING CHAPTER 1 SECTION 106.1.1. | | 2. THE GAS WATER HEATER IN THE GUEST HOUSE GARAGE, SHOW | | HOW IT WILL BE VENTED TO THE OUTSIDE. PROVIDE | | MANUFACTURE'S SPECIFICATIONS. | | 3. THE RISER DIAGRAM DOES NOT MATCH THE FLOOR PLANS. | | A) BOTH 2ND FLOOR BATHROOMS HAVE 2-LAVATORYS | | B) MASTER BATH IS MISSING A TUB. | | C) BACK BATHROOM IS MISSING THE 2 LAVS. AND | | HAS AN EXTRA SHOWER. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|