Plan Review Notes
Plan Review Notes For Permit 08020067
Permit Number 08020067
Review Stop P
Sequence Number 1
Notes
Date Text
2008-02-08 08:34:40DENIED;
 1. ADDRESS OF JOB ISREQUIRED ON ALLPAGES OF
 PLANS.FBC BUILDING CHAPTER 1 SECTION 106.1.1.
 2. THE GAS WATER HEATER IN THE GUEST HOUSE GARAGE, SHOW
 HOW IT WILL BE VENTED TO THE OUTSIDE. PROVIDE
 MANUFACTURE'S SPECIFICATIONS.
 3. THE RISER DIAGRAM DOES NOT MATCH THE FLOOR PLANS.
 A) BOTH 2ND FLOOR BATHROOMS HAVE 2-LAVATORYS
 B) MASTER BATH IS MISSING A TUB.
 C) BACK BATHROOM IS MISSING THE 2 LAVS. AND
 HAS AN EXTRA SHOWER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695