2008-02-07 10:02:58PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MAIN HOUSE AND THE GUEST HOUSE CAN NOT BE ON THE
 SAME ENERGY CALCULATION. PLEASE SUBMIT SEPARATE ENERGY
 CALCULATIONS FOR EACH BUILDING, SEE 2004 FBC
 13-101.2.5.1.
  
 2) PLEASE HAVE THE REVISED ENERGY CALCULATIONS SIGNED
 BY OWNER/AGENT ALSO, SEE 2004 FBC 13-600.3.ABC.2.
  
 3) ENERGY CALCULATIONS LINE 8B DOES NOT SHOW THE RAISED
 WOOD FLOOR OR INSULATION, SEE 2004 FBC 13-605.2.A.1.1
 AND 13-605.1.C.2. PLEASE CORRECT ALSO THE PLANS IF
 NEEDED.
  
 4) SHOW AN A/C EQUIPMENT SCHEDULE WITH ALL THE
 PERTINENT INFORMATION ON THE MECHANICAL PLAN, SEE 2004
 WPB AMEND. 106.3.5.4 (10).
  
 5) SHOW ALL THE BATHROOM EXHAUST FANS ON THE MECHANICAL
 PLAN AS THEY ARE ON THE ELECTRICAL PLAN, SEE 2004 FBC/R
 R303.3 EXCEPT.
  
 6) SHOW THE LOCATION OF THE GUEST HOUSE A/C CONDENSER
 UNIT ON THE MECHANICAL AND ELECTRICAL PLANS, SEE 2004
 FBC/R M1307.
  
 7) A/C SYSTEM 2 COOLING LOAD CALCULATIONS ARE CALLING
 FOR 23,601 TOTAL COOLING BTU'S. A 3 TON A/C SYSTEM AT
 34,200 TOTAL COOLING BTU'S WOULD BE TO LARGE AS YOU CAN
 ONLY GO 15% OVER THE COOLING LOAD CALCULATION, SEE 2004
 FBC 13-607.1.ABC.1.1. PLEASE CORRECT.
  
 8) A/C SYSTEM 3 COOLING LOAD CALCULATIONS ARE CALLING
 FOR 23,046 TOTAL COOLING BTU'S. A 3 TON A/C SYSTEM AT
 34,200 TOTAL COOLING BTU'S WOULD BE TO LARGE AS YOU CAN
 ONLY GO 15% OVER THE COOLING LOAD CALCULATION, SEE 2004
 FBC 13-607.1.ABC.1.1. PLEASE CORRECT.
  
 9) ELECTRICAL PLAN E-2 IS SHOWING A GAS INSTA-HOT WATER
 HEATER IN THE GARAGE OF THE GUEST HOUSE, THIS MAY BE A
 CONFINED SPACE. PLEASE SUBMIT COMBUSTION AIR
 CALCULATIONS, SEE 2004 FBC/R G2407.5.
  
 10) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 GAS INSTA-HOT WATER HEATER AND ALL OTHER GAS APPLIANCES
 BEING INSTALLED.
  