| APPLICATION #08020067 |
| ELECTRICAL PLAN REVIEW |
| 270 BARCELONA ROAD |
| 2/6/08 |
| WEST PALM BEACH, FL. |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| ON SHEET E2: |
| |
| 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| SIZE AND TYPE, GROUNDING DETAILS, SERVICE EQUIPMENT AND |
| PANEL LOCATIONS PER 215.5 NEC AND 106.3.5.4 FBC. |
| INDICATE WHICH IS NEW AND WHICH IS EXISTING. THIS |
| INCLUDES THE GUEST HOUSE. |
| |
| 2} THE LOAD CALCULATION TABLE ON SHEET E2 INDICATES THE |
| ?GENERAL LIGHTING? LOADS TO BE ON 20 AMP CIRCUITS WITH |
| #14 AWG CONDUCTORS IN VIOLATION OF 310.16, MUST BE #12 |
| CONDUCTORS OR 15 AMP BREAKERS WHERE ALLOWED. ALSO NOTE |
| THAT THE TABLE INDICATES 21 OF THOSE BRANCH CIRCUITS. |
| |
| 3} THE THREE SMALL APPLIANCE CIRCUITS LISTED IN THE |
| CALCULATION TABLE, ARE CALCULATED AT 1200VA, THOSE |
| CIRCUITS ARE REQUIRED TO BE CALCULATED AT 1500VA PER |
| 220.52. ALSO NOTE THERE ARE ONLY TWO SMALL APPLIANCE |
| CIRCUITS LISTED ON THE PANEL SCHEDULES, CORRELATE SAME. |
| NOTE: SEE 210.11(C)(1), TWO PER KITCHEN REQUIRED, CHECK |
| PANEL SCHEDULES. |
| |
| 4} THE GFI?S LISTED AT 3000 VA EACH IN THE CALCULATION |
| TABLE, ARE IN VIOLATION OF 210.20(B)(1), 210.21(B)(2), |
| AND 310.16, AS THOSE CIRCUITS WOULD NEED TO BE RATED |
| FOR 25 AMPS. |
| |
| 5} THE RANGE IS LISTED AS 2.6 KVA ON A 30 AMP CIRCUIT |
| IN PANEL ?A?, CORRELATE WITH THE LOAD CALCULATION, ALSO |
| SEE 422.11(A). |
| |
| 6} THE WATER HEATERS LISTED IN PANELS ?A? AND ?C? ARE |
| LISTED AS 2.6 KVA ON A 30 AMP CIRCUIT, SEE COMMENT #5. |
| |
| 7} THERE ARE TWO ?APPLIANCE? CIRCUITS IN BOTH PANELS |
| ?A? AND ?C? @2.6 KVA ON A 20 AMP CIRCUIT IN VIOLATION |
| OF 310.16, 210.20(B)(1), AND 210.21(B)(2). INDICATE |
| WHAT THESE ?APPLIANCES? ARE ON THE SCHEDULES, SEE |
| 408.4.- NEW VERBAGE FOR 2005 NEC: "THE IDENTIFICATION |
| SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT |
| TO BE DISTINGUISHED FROM ALL OTHERS." |
| |
| 8} THERE IS ONE DISHWASHER IN THE LOAD CALCULATIONS |
| LISTED AS 1200 VA, THERE ARE TWO ON THE PANEL SCHEDULES |
| (A & C) LISTED AT 1500 VA, CORRELATE SAME. |
| |
| 9} THE DISPOSAL IN THE CALCULATION IS LISTED AT 900 VA, |
| AND LISTED AS 1500 VA ON A 20 AMP CIRCUIT, IN PANEL |
| SCHEDULE ?A?. |
| |
| 10} THE DRYER IN PANEL SCHEDULE ?A? IS LISTED AT 2600 |
| VA, OR 10.8 AMPS, ON A 30 AMP CIRCUIT, AND 5000 VA IN |
| THE CALCULATIONS, CORRELATE SAME. |
| |
| 11} THE ATTIC IN THE GUEST HOUSE MUST COMPLY WITH |
| 210.63 AND 210.70(A)(3) SINCE MECHANICAL EQUIPMENT WILL |
| BE INSTALLED. |
| |
| 12} THERE ARE TWO A/C AND AHU?S LISTED AS #1. |
| |
| SHEET E1: GIVEN THE FACT THAT THERE IS NO WAY TO |
| DETERMINE NEW FROM EXISTING, THIS REVIEW IS DONE AS IF |
| ALL WORK IS NEW |
| |
| 1} THE DISCONNECTS FOR THE CONDENSING UNITS DO NOT |
| COMPLY WITH 110.26 CLEARANCE REQUIREMENTS. NOTE, ONLY |
| TWO SHOWN, THREE IN THE SCHEDULES. |
| |
| 2} R313.1.1 RESIDENTIAL BUILDING CODE, SMOKE ALARMS |
| SHALL BE LOCATED AS REQUIRED IN NEW DWELLINGS WHEN |
| REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR. SEE |
| ARTICLE FOR COMPLETE TEXT. TWO ARE MISSING FROM THE |
| UPPER BEDROOMS, AND ONE DOWNSTAIRS, SEE REVIEWED PLAN. |
| ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 |
| NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID |
| CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE |
| LOCATIONS OF THE SOUNDING DEVICES. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| |