 ELECTRICAL PLAN REVIEW
 270 BARCELONA ROAD
 2/6/08
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ON SHEET E2:
  
 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, SERVICE EQUIPMENT AND
 PANEL LOCATIONS PER 215.5 NEC AND 106.3.5.4 FBC.
 INDICATE WHICH IS NEW AND WHICH IS EXISTING. THIS
 INCLUDES THE GUEST HOUSE.
  
 2} THE LOAD CALCULATION TABLE ON SHEET E2 INDICATES THE
 ?GENERAL LIGHTING? LOADS TO BE ON 20 AMP CIRCUITS WITH
 #14 AWG CONDUCTORS IN VIOLATION OF 310.16, MUST BE #12
 CONDUCTORS OR 15 AMP BREAKERS WHERE ALLOWED. ALSO NOTE
 THAT THE TABLE INDICATES 21 OF THOSE BRANCH CIRCUITS.
  
 3} THE THREE SMALL APPLIANCE CIRCUITS LISTED IN THE
 CALCULATION TABLE, ARE CALCULATED AT 1200VA, THOSE
 CIRCUITS ARE REQUIRED TO BE CALCULATED AT 1500VA PER
 220.52. ALSO NOTE THERE ARE ONLY TWO SMALL APPLIANCE
 CIRCUITS LISTED ON THE PANEL SCHEDULES, CORRELATE SAME.
 NOTE: SEE 210.11(C)(1), TWO PER KITCHEN REQUIRED, CHECK
 PANEL SCHEDULES.
  
 4} THE GFI?S LISTED AT 3000 VA EACH IN THE CALCULATION
 TABLE, ARE IN VIOLATION OF 210.20(B)(1), 210.21(B)(2),
 AND 310.16, AS THOSE CIRCUITS WOULD NEED TO BE RATED
 FOR 25 AMPS.
  
 5} THE RANGE IS LISTED AS 2.6 KVA ON A 30 AMP CIRCUIT
 IN PANEL ?A?, CORRELATE WITH THE LOAD CALCULATION, ALSO
 SEE 422.11(A).
  
 6} THE WATER HEATERS LISTED IN PANELS ?A? AND ?C? ARE
 LISTED AS 2.6 KVA ON A 30 AMP CIRCUIT, SEE COMMENT #5.
  
 7} THERE ARE TWO ?APPLIANCE? CIRCUITS IN BOTH PANELS
 ?A? AND ?C? @2.6 KVA ON A 20 AMP CIRCUIT IN VIOLATION
 OF 310.16, 210.20(B)(1), AND 210.21(B)(2). INDICATE
 WHAT THESE ?APPLIANCES? ARE ON THE SCHEDULES, SEE
 408.4.- NEW VERBAGE FOR 2005 NEC: "THE IDENTIFICATION
 SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT
 TO BE DISTINGUISHED FROM ALL OTHERS."
  
 8} THERE IS ONE DISHWASHER IN THE LOAD CALCULATIONS
 LISTED AS 1200 VA, THERE ARE TWO ON THE PANEL SCHEDULES
 (A & C) LISTED AT 1500 VA, CORRELATE SAME.
  
 9} THE DISPOSAL IN THE CALCULATION IS LISTED AT 900 VA,
 AND LISTED AS 1500 VA ON A 20 AMP CIRCUIT, IN PANEL
 SCHEDULE ?A?.
  
 10} THE DRYER IN PANEL SCHEDULE ?A? IS LISTED AT 2600
 VA, OR 10.8 AMPS, ON A 30 AMP CIRCUIT, AND 5000 VA IN
 THE CALCULATIONS, CORRELATE SAME.
  
 11} THE ATTIC IN THE GUEST HOUSE MUST COMPLY WITH
 210.63 AND 210.70(A)(3) SINCE MECHANICAL EQUIPMENT WILL
 BE INSTALLED.
  
 12} THERE ARE TWO A/C AND AHU?S LISTED AS #1.
  
 SHEET E1: GIVEN THE FACT THAT THERE IS NO WAY TO
 DETERMINE NEW FROM EXISTING, THIS REVIEW IS DONE AS IF
 ALL WORK IS NEW
  
 1} THE DISCONNECTS FOR THE CONDENSING UNITS DO NOT
 COMPLY WITH 110.26 CLEARANCE REQUIREMENTS. NOTE, ONLY
 TWO SHOWN, THREE IN THE SCHEDULES.
  
 2} R313.1.1 RESIDENTIAL BUILDING CODE, SMOKE ALARMS
 SHALL BE LOCATED AS REQUIRED IN NEW DWELLINGS WHEN
 REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR. SEE
 ARTICLE FOR COMPLETE TEXT. TWO ARE MISSING FROM THE
 UPPER BEDROOMS, AND ONE DOWNSTAIRS, SEE REVIEWED PLAN.
 ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER