 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 SUBMIT THE FOLLOWING FOR REVIEW
  
 1} THIS APPLICATION INVOLVES SUB.METERING. IT IS THE
 DETERMINATION OF THIS OFFICE THAT ELECTRICALLY THE
 PLANS COMPLY WITH CODE IF THE LUGS IN THE 400 AMP METER
 ARE CORRECT FOR THE TAP PROPOSED. INDICATE WHICH TAP
 RULE IS BEING INVOLKED (PROVIDE CODE ARTICLE).
  
 2} SUBMIT A NOTORISED LETTER FROM THE OWNER OF THE
 EXISTING SERVICE, GRANTING PERMISSION FOR THE SUB
 METER.INDICATE WHERE THE EXISTING DISCONNECTING MEANS
 FOR THE 400 AMP SERVICE IS LOCATED, BOTH ON THE RISER
 AND ON A SITE PLAN, ALSO LOCATING THE PROPOSED
 EQUIPMENT ON THE SITE PLAN THAT COMPLIANCE WITH
 230.72(A)MAY BE REVIEWED.
  
 3} FOR RECORD RETENTION, THE ADDRESS OF THE JOB MUST BE
 ON THE PLANS. 106.1.3 FBC AS AMENDED.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  