2008-02-04 14:14:04 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT | | SIZE AND TYPE, GROUNDING DETAILS, SERVICE EQUIPMENT AND | | PANEL LOCATIONS PER 106.3.5.4 FBC, 215.15 AND 230 NEC. | | | | 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 | | RESIDENTIAL FLORIDA BUILDING CODE.LOCATE SAME ON A | | FLOOR PLAN. | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | 106.1.3.FBC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|