Plan Review Notes
Plan Review Notes For Permit 08020013
Permit Number 08020013
Review Stop B
Sequence Number 2
Notes
Date Text
2008-02-19 10:55:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PLEASE REMOVE DOCUMENTS WHICH ARE NOT A PART OF THE
 PRODUCT APPROVAL.THIS REVIEW HAS BEEN DONE BASED ON
 THE MIAMIDADE NOA PROVIDED AS I CANNOT DETERMINE WHERE
 THE CUT SHEETS CAME FROM.WHEN I GO TO THE FLORIDA
 PRODUCT APPROVAL SITE, WWW.FLORIDABUILDING.ORG, IT
 APPEARS THAT MIAMIDADE NOAS WERE SUBMITTED.THEREFORE,
 COMPLIANCE WITH THIS PRODUCT APPROVAL IS REQUIRED
 UNLESS OTHER PAPERWORK IS SUBMITTED.AS DISCUSSED, THE
 INSTALLATION SCHEDULE SPECIFIES 2" GLASS SEPARATION; 2
 7/8 REQUIRED (SHEET SSHB C 050B).
  
 2.DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.THE ENGINEERING SUBMITTED ADDRESSED ONLY
 ANCHORING INTO THE EXISTING GLASS DOOR FRAME.NOTE
 THAT GLASS SEPARATION ALSO NEEDS TO BE ADDRESSED.
  
  