Plan Review Notes For Permit 08010762 |
Permit Number |
08010762 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-01-31 16:12:43 | BUILDING REVIEW CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1-THIS IS A SEPARATE PERMIT AS AGREED ON WITH | | CONTRACTOR ON PROVISO DATED 04/12/07.SEE ATTACHED | | COPY. OWES $85.14FOR PERMIT FEE BALANCE. | | | | 2- SELECTED ASSEMBLY ON PAGE 31 OF NOA 05-0830.10 | | SUBMITTED CAN'T BE USED IN THIS AREA BECAUSE IT DOESN'T | | MEET THE DESIGN PRESSURES FOR PERIMETER AND CORNER | | AREAS AND ASSEMBLY IS LIMITED BY GENERAL LIMITATION #9, | | WHICH DOESN'T ALLOW NAIL ENHANCING.NEED TO SELECT | | ASSEMBLYTHAT IS LIMITED BY GENERAL LIMITATION #7, | | WHICH ALLOWS NAIL ENHANCING. | | | | 3- PROVIDE THE RAS 117 CALCULATIONS FOR NAIL ENHANCING | | AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7. | | | | 4- THERE IS A DESIGNER OF RECORD ON THIS PROJECT. | | DESIGNER OF RECORD NEEDS TO REVIEW AND APPROVE IN | | WRITING(NOT SIGNING AND SEALING)ALL PRODUCT | | APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS | | TO FBC 2004. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|