Plan Review Notes For Permit 08010649 |
Permit Number |
08010649 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-01-31 12:51:43 | BUILDING PLAN REVIEW | | PERMIT: 08010649 | | ADD: 400 N. FLAGLER DR. | | CONT: BRANCH CONST. | | TEL: (561)833-6206 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 1ST | | ACTION: DENIED | | | | 1)2004 FBC EXISTING | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | 2)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; | | PROVIDE INFORMATION BASED ON INTERIOR FINISH | | REQUIREMENTS BASED ON OCCUPANCY. | | | | 3)WPB AMENDMENTS 106.1.2 ADDITIONAL INFORMATION IS | | REQUIRED FOR THE LINEAR DIFFUSER. SHOW THE FRAME | | OPENING DETAIL FOR THE NEW LINEAR DIFFUSER ON THE | | DRAWINGS. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|