2008-01-31 12:51:43BUILDING PLAN REVIEW
 PERMIT: 08010649
 ADD: 400 N. FLAGLER DR.
 CONT: BRANCH CONST.
 TEL: (561)833-6206
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 2)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
  
 3)WPB AMENDMENTS 106.1.2 ADDITIONAL INFORMATION IS
 REQUIRED FOR THE LINEAR DIFFUSER. SHOW THE FRAME
 OPENING DETAIL FOR THE NEW LINEAR DIFFUSER ON THE
 DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]