2008-03-07 09:25:182004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THE ROOF COMPONENT AND CLADDING PRESSURES (WIND
 LOAD) ON SHEET AO1 ARE INCORRECT. SEE FBC TABLE
 R301.2(2)OR SUBMIT SIGNED AND SEALED CALCULATIONS
 INDICATING HOW THE SPECIFIED PRESSURES WERE OBTAINED.
 FBC 106.1.2* CITY AMENDMENTS.
  
 3) THE FASTENING OPTION SPECIFIED ON PAGE 18 OF THE
 PRODUCT APPROVAL FOR THE GAF BUILT UP ROOF SYSTEM HAS A
 MAXIMUM DESIGN PRESSURE OF -75 PSF WHICH IS TOO LOW FOR
 THE CORNER AREAS OF THE FLAT ROOF WHICH HAVE AN UPLIFT
 OF -89 PSF PER TABLE R301.2(2). SUBMIT RAS 117
 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY
 LIMITATION #7 OF THE PRODUCT APPROVAL. SEE COMMENT # 18
 OF THE FIRST REVIEW. RULE 9B-72 FBC 106.1.2* CITY
 AMENDMENTS.
  
 4) NOTE: DURING THE COURSE OF THE PROJECT THE
 CONTRACTOR WILL BE REQUIRED TO PERFORM INVESTIGATIVE
 WORK TO DETERMINE THAT THE EXISTING FOOTINGS, TIE BEAMS
 AND STRUCTURE ARE ADEQUATE TO SUPPORT THE SECOND STORY
 ADDITION. ADDITIONAL DETAILS FROM THE DESIGNER OF
 RECORD MAY BE REQUIRED. FBC 106.1.2* CITY AMENDMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]