Notes |
Date |
Text |
2008-01-29 12:06:11 | ***FAILED*** | | | | | | 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION | | 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT | | PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.NOTE: | | A/C CONDENSER MUST MAINTAIN A MINIMUM SETBACK OF 8.5' | | FROM THE REAR PROPERTY LINE. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | ZONING TECHNICIAN (561)805-6720 | | | | | | | | | | | | SENT TO "M" - SF RACK |
|