2008-02-05 09:29:07PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A03 IS INDICATING IS INDICATING PRIMARY AND
 SECONDARY ROOF DRAINAGE, PLEASE PROVIDE THE FOLLOWING
 INFORMATION FOR THESE REQUIRED DRAINS.
  
 A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF
 AND VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS
 AND SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004
 PLUMBING, SECTION 1106.
 B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004
 PLUMBING, SECTION 1106.2
 C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION
 1106.4
 D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING,
 SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004
 PLUMBING, TABLE 1106.7.
 E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004
 PLUMBING, SECTION 1107.
 A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING,
 SECTION 1107.1.
 B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING,
 SECTION 1107.2.
  
 2. SHEET A05 SAITARY ISOMETRIC THE FOLLOWING
 CORRECTIONS ARE REQUIRED.
  
 (A) FBC-PLUMBING SECTION *406.3 WASTE CONNECTIONS.THE
 TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) FBC-PLUMBING SECTION *802.4 STANDPIPES.STANDPIPES
 SHALL BE INDIVIDUALLY TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 **INDICATE THE REQUIRED STANDPIPE FOR THE WASHING
 MACHINE.
  
 (C) FBC-PLUMBING SECTION *708.3.5 BUILDING DRAIN AND
 BUILDING
 SEWER JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
  
 (D) FBC-PLUMBING SECTION *708.7 MINIMUM SIZE.
 CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3".
  
 (E) FBC-PLUMBING SECTION *708.9 ACCESS. ACCESS SHALL
 BE
 PROVIDED TO ALL CLEANOUTS.
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED AT
 4' A.F.F.
  
 (F) FBC-PLUMBING SECTION *1002.3 (5) PROHIBITED TRAPS.
 THE "S" TRAP BEING INDICATED FOR THE SINK IS PROHIBITED
 AND A VENT IS REQUIRED FOR THE SINK PER FBC-PLUMBING
 SECTION *901.2.1 VENTING REQUIRED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  