Plan Review Notes
Plan Review Notes For Permit 08010640
Permit Number 08010640
Review Stop M
Sequence Number 1
Notes
Date Text
2008-01-29 14:54:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 2) PLEASE SHOW ON MECHANICAL PLAN PAGE 05, ALL REGISTER
 (GRILL) SIZES, AND ALL DUCK WORK WITH SIZES (SUPPLY AND
 RETURN), SEE 2004 WPB AMEND. 106.3.5.4 (10).
  
 3) THE GAS CLOTHES DRYER IS IN A CONFINED SPACE PLEASE
 SUBMIT COMBUSTION AIR CALCULATIONS AND PROVIDE
 COMBUSTION AIR, SEE 2004 FBC/R G2407.1 AND G2407.5.1.
  
 4) I WAS NOT ABLE TO FIND THE TRANE A/C SYSTEM LISTED
 ON THE PLAN IN THE ARI DIRECTORY WEB-SITE, PLEASE CHECK
 MODEL NUMBERS AND CORRECT OR SUBMIT AN ARI CERTIFICATE,
 SEE 2004 FBC 13607.1.AGC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]