Date |
Text |
2008-03-05 19:45:12 | ** DENIED2ND REVIEW ** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING. |
| |
| 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS REVIEW WITH |
| RESPECT TO LIGHTING PERFORMANCE CALCULATIONS TO BE |
| SUBMITTED AND SHOWN ON PLANS. 13-415.2, |
| 13-415.2.ABC.1.1. |
| (THIS IS NOT ENERGY CALCULATIONS) |
| PLEASE KNOW AS FIXTURES ARE BEING REMOVED, NEW BOXES |
| ARE BEING RELOCATED AND NEW TO BE INSTALLED, THIS IS |
| NEW INSTALLATION OF LIGHTING FIXTURES. |
| THIS IS NOT ONLY TAKING DOWN EXISTING FIXTURES AND |
| PLACING BACK ON THE SAME BOXES AND SAME LOCATIONS. |
| ** THESE ARE CONSIDERED NEW AND MINIMUM ON PLANS IS |
| REQUIRED. |
| PLEASE KNOWAS ELECTRICAL IS ON THE SAME SHEETS WITH |
| ARCHITECTURAL ONLY IF ALL OTHER REVIEWS PASS A |
| *PROVISO* MAY BE SET UP TO SUBMIT REVISIONS WITHIN |
| 30DAYS OF ISSUANCE OF PERMIT. |
| IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL OR TO GO |
| OVER NEEDED INFORMATION ON PLANS FOR LPD. |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |