2008-01-31 14:09:57 | ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE SUBMIT THE LIGHTING PERFORMANCE LEVELS |
| FOR DINING SPACE/AREA PER 13-415.2 |
| PLEASE LIST THE FIXTURES BEING USED. |
| |
| 2) NOTE: PLEASE INDICATE THE LOCATIONS OF NEW OR |
| EXISTING EXIT AND EMERGENCY LIGHTING PER NFPA-101 7.8, |
| 7.9 |
| |
| 3) NOTE: PLEASE LIST THE FOLLOWING CODES ON PLANS FOR |
| ELECTRICAL. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| |
| 4) NOTE: PLEASE KNOW ONLY TWO SETS OF SIGNED, SEALED |
| DATED PLANS ARE NEEDED. PLEASE SEE 5 SETS WERE |
| SUBMITTED. UP TO THREE SETS SIGNED AND SEALED MAY BE |
| SUBMITTED FOR REVIEW AND STAMPING IF EXTRA COPY IS |
| DESIRED BY CONTRACTOR HOWEVER AS STATED ONLY TOW ARE |
| NEEDED. |
| THIS IS FOR INFORMATION ONLY AS TWO SETS WERE SIGNED |
| AND SEALED. |
| |
| ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| CONTACTING THIS REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |