Plan Review Notes
Plan Review Notes For Permit 08010617
Permit Number 08010617
Review Stop B
Sequence Number 1
Notes
Date Text
2008-01-29 16:34:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SHUTTER SPAN FOR ACCORDION SHUTTERS SHOULD
 CORRELATE WITH THE OPENING HEIGHT (BLADE LENGTH).
 PLEASE REVISE INSTALLATION SCHEDULE.
  
 2.SEE OPENING 5.AN OPENING OF 57", WITH 3" EDGE
 DISTANCE TOP AND BOTTOM, SHOULD HAVE A SPAN OF
 APPROXIMATELY 61".SEE THE ANCHOR CHART ON SHEET 8.
 YOU HAVE HIGHLIGHTED THE "CONCRETE" COLUMN BUT SHOULD
 BE USING THE "MASONRY" COLUMN AS YOU HAVE SPECIFIED
 BLOCK AS THE SUBSTRATE ON THE INSTALLATION SCHEDULE. 7"
 SPACING IS REQUIRED FOR THE BOTTOM.
  
 3.SEE OPENING 8.FOR A SPAN OF APPROXIMATELY 110",
 (NOTE THAT YOU STATE IT IS 320", PLEASE REVISE) YOU
 MUST USE THE COLUMN FOR NOTE 3, 3 1/2" AND 5" ANCHOR
 SPACING REQUIRED.IF THE SUBSTRATE IS CONCRETE, 9" AND
 6" REQUIRED, NOT 9" AND 9" AS SPECIFIED ON THE
 INSTALLATION SCHEDULE.
  
 4.PLEASE CHECK ALL OPENINGS; THESE COMMENTS MAY APPLY
 TO OTHER OPENINGS AS NOT ALL WERE CHECKED.