Plan Review Notes
Plan Review Notes For Permit 08010582
Permit Number 08010582
Review Stop B
Sequence Number 1
Notes
Date Text
2008-01-31 16:52:30 
  
 DENIED
  
  
 1)CONSTRUCTION DOCUMENTS SHALL SHOW THE SIZE, SECTION
 AND RELATIVE LOCATIONS OF STRUCTURAL MEMBERS WITH FLOOR
 LEVELS, COLUMN CENTERS AND OFFSETS FULLY DIMENSIONED.
 THE DESIGN LOADS AND OTHER INFORMATION PERTINENT TO THE
 STRUCTURAL DESIGN REQUIRED BY SECTIONS 1603.1.1 THROUGH
 1603.1.8 SHALL BE CLEARLY INDICATED ON THE CONSTRUCTION
 DOCUMENTS FOR PARTS OF THE BUILDING OR STRUCTURE, PER
 1603.1 FBC.(WIND LOADS, FLOOR LOADS,
 SOIL BEARING PRESSURE AND DESIRED SOIL DENSITY FOR
 FOUNDATIONS, ETC.)
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 3)MORE INFORMATION IS REQUIRED:
 A) SHOW LOCATION OF WORK IN RELATION TO ENTIRE
 BUILDING
 B) IS THEIR AN EXISTING FOUNDATION UNDER 8" CBS WALL
 AND IF SO IS THE 30"X30" PAD ATTACHED OR UNDERNEATH
 EXISTING
 C) WILL BEAM SET ON CBS WALL, IN A POCKET OR AS NOTE
 STATES ON A 4X4 COLUMN
 D) PROVIDE CORRECT ADDRESS ON DRAWINGS
  
 4)PROVIDE PRODUCT APPROVALS FOR SIMPSON TIES. PLEASE
 NOTE THAT HGMA10 IS A WOOD TO MASONRY/CONCRETE
 APPLICATION AND YOUR JOIST TO BEAM IS AN ALL WOOD
 CONDITION
  
 BLDG PLAN REVIEW