2008-01-24 10:35:39 | 2004 FBC W/2007 REVISIONS |
| INSTALL ROOF NEW CONSTRUCTION |
| |
| DENIED BY BUILDING |
| |
| 1) THE TAMKO MODIFIED SYSTEM SPECIFIED ON PAGE 6 OF NOA |
| 07-0111.03 IS FOR INSULATED WOOD DECKS AND IS NOT THE |
| ONE THAT WAS APPROVED WITH THE MASTER PERMIT. THE ONE |
| THAT WAS APPROVED IS ON PAGE 17 AND IS FOR |
| NON-INSULATED WOOD DECKS. THEREFORE, RAS 117 ENHANCED |
| FASTENING CALCULATIONS FOR THE NEW SYSTEMS ANCHOR SHEET |
| IS REQUIRED TO BE SUBMITTED. THE APPLICATION SPECIFIES |
| 1/4" TAPERED INSULATION TO BE INSTALLED AND THE |
| ASSEMBLY SELECTED ON PAGE 6 OF THE NOA REQUIRES A |
| MINIMUM 1/2" THICK INSULATION. PLEASE REVISE AND |
| SPECIFY WHICH ONE OF THE LISTED INSULATIONS WILL BE |
| USED. |
| |
| 2) THE HYDRO-STOP LIQUID APPLIED MEMBRANE ROOFING THAT |
| WAS SUBMITTED IS NOT THE PRODUCT ( SEALOFLEX NOA NO. |
| 05-0901.04) THAT WAS APPROVED WITH THE MASTER PERMIT. |
| THE PRODUCT APPROVAL SUBMITTED FOR THE HYDRO-STOP |
| REQUIRES INSULATION FOR ALL APLICATIONS. SPECIFY THE |
| SYSTEM AMD DESIGN PRESSURE FOR THE ASSEMBLY THAT WILL |
| BE INSTALLED. SUBMIT SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR ENHANCED FASTENING FROM A FLORIDA |
| REGISTERED ENGINEER, ARCHITECT OR REGISTERED ROOF |
| CONSULTANT AS REQUIRED BY LIMITATION #7 ON PAGE 8 OF |
| THE PRODUCT APPROVAL. |
| |
| 3) SUBMIT PRODUCT APPROVAL FOR THE POLYGLASS TU PLUS. |
| |
| 4) PRODUCT APPROVALS THAT ARE SUBMITTED WHICH ARE |
| DIFFERENT FROM THE APPROVED ONES WILL BE CHARGED A |
| REVISION FEE. |
| |