Plan Review Notes
Plan Review Notes For Permit 08010468
Permit Number 08010468
Review Stop M
Sequence Number 4
Notes
Date Text
2008-07-08 11:20:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN M-2
 *** DENIED ***
 1) PLAN SHOWS A RETURN AIR TRANSFER DUCT (SEE YELLOW
 HIGH LIGHT ON PLAN) FROM THE WEST CORRIDOR TO WAITING
 AREA 1802, AS THAT WALL IS RATED PLEASE COMPLY WITH
 2004 FBC/M 607.5.3. ALSO SHOW THE SIZE OF THE DUCT.
  
 2) THE 28X12 HIGH PRESSURE DUCT (SEE YELLOW HIGH LIGHT
 ON PLAN) THAT IS BEING ALTERED AT THE RATED WALL TO
 WAITING AREA 1816 IS PENETRATING A RATED WALL AND NEED
 TO COMPLY WITH 2004 FBC/M 607.5.3.
  
 **2004 FBC/M 607.5.3 FIRE PARTITIONS. DUCT PENETRATIONS
 IN FIRE PARTITIONS SHALL BE PROTECTED WITH APPROVED
 FIRE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR
 LISTING, OR MEET THE EXCEPTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]