Plan Review Notes For Permit 08010468 |
Permit Number |
08010468 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2008-07-08 11:20:37 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | REVISION TO MECHANICAL PLAN M-2 | | *** DENIED *** | | 1) PLAN SHOWS A RETURN AIR TRANSFER DUCT (SEE YELLOW | | HIGH LIGHT ON PLAN) FROM THE WEST CORRIDOR TO WAITING | | AREA 1802, AS THAT WALL IS RATED PLEASE COMPLY WITH | | 2004 FBC/M 607.5.3. ALSO SHOW THE SIZE OF THE DUCT. | | | | 2) THE 28X12 HIGH PRESSURE DUCT (SEE YELLOW HIGH LIGHT | | ON PLAN) THAT IS BEING ALTERED AT THE RATED WALL TO | | WAITING AREA 1816 IS PENETRATING A RATED WALL AND NEED | | TO COMPLY WITH 2004 FBC/M 607.5.3. | | | | **2004 FBC/M 607.5.3 FIRE PARTITIONS. DUCT PENETRATIONS | | IN FIRE PARTITIONS SHALL BE PROTECTED WITH APPROVED | | FIRE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR | | LISTING, OR MEET THE EXCEPTIONS. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|