Plan Review Notes
Plan Review Notes For Permit 08010468
Permit Number 08010468
Review Stop E
Sequence Number 2
Notes
Date Text
2008-06-19 10:25:00** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE COMMENTS FROM *PROVISO* ISSUED ON
 PLANS 1/29/08. THE FOLLOWING WORDING IS TAKEN FROM THAT
 REVIEW.
  
  
 ** PROVISO/REVISION NEEDED **
  
 ** PLEASE SEE THE FOLLOWING ITEMS WERE REDLINED ON
 PLANS OR NEED TO BE UPDATED BEFORE FINAL ELECTRICAL
 INSPECTION.
 ** PLEASE KNOW ANY OTHER REVISIONS SHALL BE SUBMITTED
 BEFORE ROUGH ELECTRICAL INSPECTION.
  
 ** ALL REVISED PLANS FOR ROUGH OR FINAL ARE REQUIRED TO
 BE ON-SITE FOR ELECTRICAL INSPECTOR STAMPED AS REVIEWED
 BY PLAN REVIEW.
  
 1) NOTE: PLEASE SEE THE CODE SECTION NOTED FOR
 EMERGENCY LIGHTS AHEAD OF LOCAL BRANCH CIRCUITS ON
 SHEETS E-4 AND E-6 (NOTE #2) CHANGED IN THE 2005 NEC TO
 700.12(F).
  
 2) NOTE: PLEASE LIST MAXIMUM TIMES FOR OCCUPANCY SENSOR
 TYPE DEVICES PER 13-415.1.ABC.1.1 AND .1.2. MAXIMUM
 TIMES REDLINED ON PLANS AS 30MINS AFTER THE LAST
 SENSING OF AN OCCUPANT.
  
 3) NOTE: PLEASE KNOW THE PANEL SCHEDULES FOR NEW
 CIRCUITING WILL BE REQUIRED TO BE REVISED TO SPECIFIC
 TO ROOMS AND AREAS IN WHICH THEY FEED.THIS SHOULD BE
 DONE BY ROOM NAME/NUMERICAL DESIGNATIONS AS LISTED ON
 PLANS.
 FOR EXAMPLE: ROOM 1824/PANTRY RECEPTS, ROOM 1822
 LIBRARY RECEPTS, LIGHTS ROOM 1942/LIBRARY, ETC. THIS IS
 FOR JOB-SITE AS WELL AS FINAL RECORD PLANS FOR *NEW
 CIRCUITS* AND *RE-LOCATED* CIRCUITS WHICH MAY BE
 AFFECTED BY CONSTRUCTION SCOPE OF WORK.
 NEC 408.4
 FBC ADMIN SECTION, 106.1.2, 106.3.5.1.2, 106.5
  
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 OFFICE/REVIEW AT THE CONTACT INFORMATION BELOW.
  