2008-05-05 16:37:52GAS PLAN REVIEW:
 DENIED 2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS GAS REVIEW COMMENTS FOR THE PURPOSE OF
 CONTINUITY.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. PER SECTION 401.1 SCOPE.
 **THIS INCLUDES THE EXISTING GAS SYSTEM. SEE PERMIT
 INFORMATION INDICATING EXISTING GAS TO SAID ADDRESS
 ATTACHED TO THESE COMMENTS.
  
 **NOTE: THE GAS ISOMETRIC RISER DIAGRAMS BY FLORIDA
 PUBLIC UTILITIES CO. PERMIT #08040547 SUBMITTED WITH
 THIS GEN/RES PERMIT APPLICATION ARE NOT INDICATING ANY
 GAS PIPING TO THE PROPOSED GENERATOR. THE ONLY NEW GAS
 PIPING BEING INDICATED IS TO A NEW 99,000 BTU RINNAI.
 PLEASE CORRECT THE GAS ISOMETRIC TO INCLUDE THE
 PROPOSED GENERATOR. THE GAS ISOMETRIC IS NOT INDICATING
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE
 PLEASE REFERENCE THE RED CIRCLED YELLOW HIGH LIGHTED
 AREAS INDICATING THIS. THE ONLY CORRESPONDING LENGTH TO
 CUT SECTION OF PIPE FOR "NEW" WORK IS FOR THE
 UNDERGROUND PIPING TO THE RINNAI. WHAT ARE THE
 CORRESPONDING LENTHS TO THE ABOVE GROUND CUT SECTIONS
 OF PIPE AND THE MISSING GAS PIPE FOR THE PROPOSED
 GENERATOR? PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 **NOTE: THE GAS ISOMETRC RISER DIAGRAMS BY FLORIDA
 PUBLIC UTILITIES CO. ARE NOT INDICATING THE ABOVE
 GROUND PIPING MATERIAL TO THE NEW 99,000 RINNIA AND
 THERE IS NO INDICATION FOR GAS PIPING OR MATERIALS FOR
 THE PROPOSED GENERATOR. PER FBC-2004 FUEL GAS SECTION
 401.1 SCOPE.
  
 3. "OK" COMMENT ADDRESSED.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **THIS INCLUDES THE EXISTING GAS SYSTEM. REFERENCE
 COMMENT #1.
  
 **NOTE: THE GAS ISOMETRIC RISER DIAGRAMS BY FLORIDA
 PUBLIC UTILITIES CO. ARE NOT INDICATING THE BTU LOAD
 FOR THE PROPOSED GENERATOR. PLEASE REFERENCE COMMENTS
 #1 AND 2 AND COMPLY.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **THIS INCLUDES THE EXISTING GAS SYSTEM. REFERENCE
 COMENT #1.
  
 **NOTE: PLEASE REFERENCE COMMENT #1, 2 AND 4 AND
 COMPLY.
  
 6. "OK" COMMENT ADDRESSED.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **PLEASE SUBMIT TWO COPIES OF MANUFACTURER'S
 SPECIFICATION SHEETS FOR THE GENERATOR CLEARLY
 INDICATING THE MODEL NUMBER, BTU LOAD CAPACITY WITH
 GENERATOR RUNNING @ 100%, AND A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY.
 NOTE: EXISTING GAS SYSTEM WAS LP/GAS, IF GAS TO
 PROPOSED GENERATOR IS ALSO LP/GAS PLEASE SUBMIT TWO
 COPIES OF MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 REQUIRED 2ND STAGE REGULATOR CLEARLY INDICATING THE
 MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 **NOTE: THE RESUBMITTED MANUFACTURER'S SPECIFICATION
 SHEETS FOR THE PROPOSED GENERATOR ARE NOT CLEARLY
 INDICATING THE BTU CAPACITY WITH THE GENERATOR RUNNING
 AT 100% AND THERE ARE NOT TWO COPIES OF MANUFACTURER'S
 SPECIFICATION SHEETS FOR THE 2ND STAGE REGULATOR BEING
 INDICATED ON THE GAS ISOMETRIC WITH THE MAKE, MODEL
 NUMBER, BTU LOAD CAPACITY AND A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL).
  
 8. "OK" COMMENT ADDRESSED.
  
 9. "OK" COMMENT ADDRESSED.
  
 10. "OK" COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  