2008-05-05 16:37:52 | GAS PLAN REVIEW: |
| DENIED 2ND TIME: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| THE PREVIOUS GAS REVIEW COMMENTS FOR THE PURPOSE OF |
| CONTINUITY. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. PER SECTION 401.1 SCOPE. |
| **THIS INCLUDES THE EXISTING GAS SYSTEM. SEE PERMIT |
| INFORMATION INDICATING EXISTING GAS TO SAID ADDRESS |
| ATTACHED TO THESE COMMENTS. |
| |
| **NOTE: THE GAS ISOMETRIC RISER DIAGRAMS BY FLORIDA |
| PUBLIC UTILITIES CO. PERMIT #08040547 SUBMITTED WITH |
| THIS GEN/RES PERMIT APPLICATION ARE NOT INDICATING ANY |
| GAS PIPING TO THE PROPOSED GENERATOR. THE ONLY NEW GAS |
| PIPING BEING INDICATED IS TO A NEW 99,000 BTU RINNAI. |
| PLEASE CORRECT THE GAS ISOMETRIC TO INCLUDE THE |
| PROPOSED GENERATOR. THE GAS ISOMETRIC IS NOT INDICATING |
| CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE |
| PLEASE REFERENCE THE RED CIRCLED YELLOW HIGH LIGHTED |
| AREAS INDICATING THIS. THE ONLY CORRESPONDING LENGTH TO |
| CUT SECTION OF PIPE FOR "NEW" WORK IS FOR THE |
| UNDERGROUND PIPING TO THE RINNAI. WHAT ARE THE |
| CORRESPONDING LENTHS TO THE ABOVE GROUND CUT SECTIONS |
| OF PIPE AND THE MISSING GAS PIPE FOR THE PROPOSED |
| GENERATOR? PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. PER FBC-2004 FUEL |
| GAS SECTION 401.1 SCOPE. |
| |
| **NOTE: THE GAS ISOMETRC RISER DIAGRAMS BY FLORIDA |
| PUBLIC UTILITIES CO. ARE NOT INDICATING THE ABOVE |
| GROUND PIPING MATERIAL TO THE NEW 99,000 RINNIA AND |
| THERE IS NO INDICATION FOR GAS PIPING OR MATERIALS FOR |
| THE PROPOSED GENERATOR. PER FBC-2004 FUEL GAS SECTION |
| 401.1 SCOPE. |
| |
| 3. "OK" COMMENT ADDRESSED. |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| **THIS INCLUDES THE EXISTING GAS SYSTEM. REFERENCE |
| COMMENT #1. |
| |
| **NOTE: THE GAS ISOMETRIC RISER DIAGRAMS BY FLORIDA |
| PUBLIC UTILITIES CO. ARE NOT INDICATING THE BTU LOAD |
| FOR THE PROPOSED GENERATOR. PLEASE REFERENCE COMMENTS |
| #1 AND 2 AND COMPLY. |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| **THIS INCLUDES THE EXISTING GAS SYSTEM. REFERENCE |
| COMENT #1. |
| |
| **NOTE: PLEASE REFERENCE COMMENT #1, 2 AND 4 AND |
| COMPLY. |
| |
| 6. "OK" COMMENT ADDRESSED. |
| |
| 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| **PLEASE SUBMIT TWO COPIES OF MANUFACTURER'S |
| SPECIFICATION SHEETS FOR THE GENERATOR CLEARLY |
| INDICATING THE MODEL NUMBER, BTU LOAD CAPACITY WITH |
| GENERATOR RUNNING @ 100%, AND A LISTING FROM A |
| NATIONALLY RECOGNIZED TESTING LABORATORY. |
| NOTE: EXISTING GAS SYSTEM WAS LP/GAS, IF GAS TO |
| PROPOSED GENERATOR IS ALSO LP/GAS PLEASE SUBMIT TWO |
| COPIES OF MANUFACTURER'S SPECIFICATION SHEETS FOR THE |
| REQUIRED 2ND STAGE REGULATOR CLEARLY INDICATING THE |
| MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING |
| FROM A NATIONALLY RECOGNIZED TESTING LABORATORY. |
| |
| **NOTE: THE RESUBMITTED MANUFACTURER'S SPECIFICATION |
| SHEETS FOR THE PROPOSED GENERATOR ARE NOT CLEARLY |
| INDICATING THE BTU CAPACITY WITH THE GENERATOR RUNNING |
| AT 100% AND THERE ARE NOT TWO COPIES OF MANUFACTURER'S |
| SPECIFICATION SHEETS FOR THE 2ND STAGE REGULATOR BEING |
| INDICATED ON THE GAS ISOMETRIC WITH THE MAKE, MODEL |
| NUMBER, BTU LOAD CAPACITY AND A LISTING FROM A |
| NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL). |
| |
| 8. "OK" COMMENT ADDRESSED. |
| |
| 9. "OK" COMMENT ADDRESSED. |
| |
| 10. "OK" COMMENT ADDRESSED. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |