Date Text
2008-03-11 10:20:00 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC,2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} PROVIDE A RISER DIAGRAM PER 215.5 INCLUDING
 GENERATOR AND RELATED EQUIPMENT.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING
 RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S FOR THE
 GENERATOR AND TRANSFER SWITCH.THREE MODELS ARE ON THE
 SPEC SHEET SUBMITTED.
  
 3} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO
 BE SERVED. 215.5. 702.5, 2005NEC.702.5 CAPACITY AND
 RATING. AN OPTIONAL STANDBY SYSTEM SHALL HAVE ADEQUATE
 CAPACITY AND RATING FOR THE SUPPLY OF ALL EQUIPMENT
 INTENDED TO BE OPERATED AT ONE TIME.
  
 4} PROVIDE A PANEL SCHEDULE FOR THE GENERATOR PANEL.
 106.3.5.4 FBC AS AMENDED.
  
 5} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR REVIEW
 PER 106.1 FBC AS AMENDED. THE PERSON TAKING
 RESPONSIBILITY FOR THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME, ALL SHEETS, PER 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718