2008-03-11 16:17:33 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| GAS PLAN REVIEW: |
| DENIED: |
| |
| ******IMPORTANT INFORMATION****** |
| AS OF 8/25/06 GENERATOR (GEN/RES AND |
| GEN/COM) PERMIT APPLICATIONS SHALL NOT |
| BE ACCEPTED UNLESS THE ELECTRICAL INFOR- |
| MATION AND GAS (OR DIESEL) INFORMATION |
| IS ALL SUBMITTED AT THE SAME TIME. THE |
| GENERATOR, ELECTRICAL AND GAS/DIESEL IN- |
| FORMATION WILL BE ROUTED TOGETHER. THIS |
| WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY |
| THE MANUFACTURER'S SPECI- |
| FICATIONS AND INSTALLATION INSTRUCTIONS) |
| ARE AVAILABLE TO ALL PLAN REVIEWERS. |
| |
| NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING |
| CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL |
| GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL GEN/RES |
| INSPECTION. THE FOLLOWING INFORMATION IS REQUIRED FOR |
| THE GAS PERMIT APPLICATION ON THE REQUIRED GAS |
| ISOMETRIC RISER DIAGRAM. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. PER SECTION 401.1 SCOPE. |
| **THIS INCLUDES THE EXISTING GAS SYSTEM. SEE PERMIT |
| INFORMATION INDICATING EXISTING GAS TO SAID ADDRESS |
| ATTACHED TO THESE COMMENTS. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS |
| SECTION 401.1 SCOPE. |
| |
| 3. TYPE OF GAS, (LP OR NATURAL) PER FBC FUEL GAS |
| SECTION 401.1 SCOPE. |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| **THIS INCLUDES THE EXISTING GAS SYSTEM. REFERENCE |
| COMMENT #1. |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| **THIS INCLUDES THE EXISTING GAS SYSTEM. REFERENCE |
| COMENT #1. |
| |
| 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. LP GAS SPECIFY 10 |
| PSI. |
| |
| 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| **PLEASE SUBMIT TWO COPIES OF MANUFACTURER'S |
| SPECIFICATION SHEETS FOR THE GENERATOR CLEARLY |
| INDICATING THE MODEL NUMBER, BTU LOAD CAPACITY WITH |
| GENERATOR RUNNING @ 100%, AND A LISTING FROM A |
| NATIONALLY RECOGNIZED TESTING LABORATORY. |
| NOTE: EXISTING GAS SYSTEM WAS LP/GAS, IF GAS TO |
| PROPOSED GENERATOR IS ALSO LP/GAS PLEASE SUBMIT TWO |
| COPIES OF MANUFACTURER'S SPECIFICATION SHEETS FOR THE |
| REQUIRED 2ND STAGE REGULATOR CLEARLY INDICATING THE |
| MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING |
| FROM A NATIONALLY RECOGNIZED TESTING LABORATORY. |
| |
| 8. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| **NOTE: IF TANK IS EXISTING, PLEASE INDICATE THAT IT |
| IS EXISTING. |
| |
| 9. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |
| 10. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| SECTION *106.3.4.3. |
| IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |