Plan Review Notes For Permit 08010414 |
Permit Number |
08010414 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2008-07-03 14:54:44 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | REVISION TO MECHANICAL PLAN | | *** DENIED *** | | | | 1) REVISED MECHANICAL PLAN NEEDS TO BE SIGNED AND | | SEALED BY THE ENGINEER (JAMES MINGES), PER FAC | | 61G1-16.003. | | | | 2) PROVIDE FOR RETURN AIR TO BEDROOMS 1 AND 2, PER 2004 | | FBC/R M1602.4. | | | | 3) EQUIPMENT SCHEDULE SHOWS THE SYSTEM AS A 12 SEER, | | PER 2004 FBC 13-607.1.ABC.3.2.1 THE MINIMUM SEER IS 13. | | PLEASE CORRECT. | | | | 4) THE SUITE NUMBERFOR THIS UNIT IS 203 ACCORDING TO | | CITY RECORDS, PLANS SHOW THE SUITE NUMBER CHANGED TO | | 103. PLEASE CORRECT. | | | | 5) PLEASE SHOW THE SIZES OF ALL GRILLS ON THE | | MECHANICAL PLAN, PER 2004 WPB AMEND. 106.3.5.4 (10). | | | | 7) SHOW THE SIZES OF ALL THE SUPPLY AND RETURN AIR | | DUCTS ON THE MECHANICAL PLAN, AS NO DUCTS ARE SIZED ON | | THIS PLAN, PER 2004 WPB AMEND. 106.5.4.3 (10). | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|