Plan Review Notes
Plan Review Notes For Permit 08010414
Permit Number 08010414
Review Stop M
Sequence Number 4
Notes
Date Text
2008-07-03 14:54:44PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN
 *** DENIED ***
  
 1) REVISED MECHANICAL PLAN NEEDS TO BE SIGNED AND
 SEALED BY THE ENGINEER (JAMES MINGES), PER FAC
 61G1-16.003.
  
 2) PROVIDE FOR RETURN AIR TO BEDROOMS 1 AND 2, PER 2004
 FBC/R M1602.4.
  
 3) EQUIPMENT SCHEDULE SHOWS THE SYSTEM AS A 12 SEER,
 PER 2004 FBC 13-607.1.ABC.3.2.1 THE MINIMUM SEER IS 13.
 PLEASE CORRECT.
  
 4) THE SUITE NUMBERFOR THIS UNIT IS 203 ACCORDING TO
 CITY RECORDS, PLANS SHOW THE SUITE NUMBER CHANGED TO
 103. PLEASE CORRECT.
  
 5) PLEASE SHOW THE SIZES OF ALL GRILLS ON THE
 MECHANICAL PLAN, PER 2004 WPB AMEND. 106.3.5.4 (10).
  
 7) SHOW THE SIZES OF ALL THE SUPPLY AND RETURN AIR
 DUCTS ON THE MECHANICAL PLAN, AS NO DUCTS ARE SIZED ON
 THIS PLAN, PER 2004 WPB AMEND. 106.5.4.3 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]