Plan Review Notes For Permit 08010414 |
Permit Number |
08010414 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-02-01 14:19:57 | ***DENIED*** | | | | 1) PLEASE REFER TO ELECTRICAL REVIEW COMMENT REGARDING | | SMOKE DETECTION DEVICES. IT WOULD BE PROBABLE THAT | | REFERENCED DEVICES ARE NOT TIED TO THE BUILDING FIRE | | ALARM SYSTEM THEREBY INDICATING SMOKE ALARMS. | | | | 2) IN ADDITION TO LOCATIONS ALREADY MENTIONED, SMOKE | | ALARMS SHALL BE A MINIMUM OF (3') FROM AC DIFFUSERS. | | | | 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|