2008-01-28 10:43:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET A-1 IS INDICATING THE APPLICABLE CODE WRONG |
| PLEASE CORRECT THE AMENDMENTS FROM 2006 TO 2007 |
| REVISIONS. PER FBC PERMIT APPLICATIONS SUBMITTED AFTER |
| 12/8/06. |
| |
| 2. SHEET P-1 IS INDICATING WH-1 IN THE NEW GARAGE: |
| PLEASE INDICATE HOW THE WATER HEATER WILL BE PROTECTED |
| FROM VEHICLE DAMAGE BY APPROVED BARRIERS. PER FBC |
| MECHANICLA SECTION * 304.4. |
| |
| 3. SHEET P-1 IS INDICATING "EXISTING SANITARY LINE TO |
| BE CAPPED OFF @ EXISTING SINK". PER FBC PLUMBING |
| SECTION *704.5 DEAD ENDS. |
| IN THE INSTALLATION OR REMOVAL OF ANY PART OF A |
| DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| CLEANOUT EXTENSIONS AND APPROVED FUTURE FIXTURE |
| DRAINAGE PIPING SHALL NOT BE CONSIDERED AS DEAD ENDS. |
| |
| 4. SHEET P-1 AND P-2 INDICATE THE REQUIRED TWO-WAY |
| CLEANOUTS PER FBC PLUMBING SECTION 708.3.5 BUILDING |
| DRAIN AND BUILDING SEWER JUNCTION. |
| |
| 5. SHEET P-1 PLEASE INDICATE THE LOCATION OF THE |
| REQUIRED (EXISTING OR NEW), 1 AUTOMATIC CLOTHES WASHER |
| CONNECTION. PER FBC PLUMBING TABLE 403.1 (R-3) ONE AND |
| TWO FAMILY DWELLINGS. |
| |
| 6. NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSES, |
| THE POOL/SPA SCOPE OF WORK WILL BE REQUIRED TO BE UNDER |
| A SEPERATE PERMIT 106.1. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |
| |
| |