2008-01-28 14:34:08PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P-3 NATURAL GAS PIPING RISER:
 SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION *401.1 SCOPE.
 *THE GAS PIPING RISER DOES NOT INDICATE CORRESPONDING
 LENGTHS TO ALL CUT SECTIONS OF PIPE. REFERENCE THE RED
 CIRCLED CUT SECTIONS THAT ARE HIGH LIGHTED YELLOW.
  
 2. SHEET P-3 NATURAL GAS PIPING RISER:
 SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS
 SECTION *401.1 SCOPE.
 *THE GAS PIPING RISER DOES NOT INDICATE THE TYPE OF
 PIPING MATERIAL BEING USED.
  
 3. SHEET P-3 NATURAL GAS PIPING RISER:
 SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 * THE ADDED SUM OF THE INDICATED CORRESPONDING LENGTHS
 TO CUT SECTIONS OF PIPING EQUALS 151', HOWEVER NOTES:
 3) DISTANCE IS INDICATING 185'. PLANS AT A MINIMUM
 SHALL BE CORRELATED. PER FBC FUEL GAS SECTION *401.1
 SCOPE.
  
 4. SHEET P-3 NATURAL GAS PIPING RISER:
 INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 * NOTES: 4) DELIVERY PRESSURE PRESSURE IS BEING
 INDICATED AS 0.8 PSI. THIS INDICATED DELIVERY PRESSURE
 IS WRONG FOR NATURAL GAS. FLORIDA PUBLIC UTILTIES CO.
 HAS 0.5, 2 OR 5 PSI DELIVERY PRESSURE.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 *PLEASE SUBMIT TWO COPIES OF MANUFACTURER
 SPECIFICATIONS ON THE PROPOSED GENERATOR INDICATING THE
 MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY AS WELL
 AS INDICATING THE MANUFACTURER SETBACK RECOMMENDATIONS
 FROM STRUCTURES.
  
 6. SUBMIT TWO COPIES OF A SITE PLAN OR SURVEY CLEARLY
 INDICATING THE LOCATION OF THE PROPOSED GENERATOR
 INDICATING A DIMENTIONS FROM PROPERTY LINES AND
 DISTANCES FROM STRUCTURES. (ZONING APPROVAL REQUIRED
 FOR PROPOSED GENERATOR LOCATION PRIOR TO GAS PERMIT
 BEING ISSUED) PER FBC FUEL GAS SECTION *401.1 SCOPE
  
 7. SHEET P-1 GAS PLAN IS CLEARLY INDICATING WHERE THE
 UNDERGROUND GAS PIPING IS BENEATH THE PROPOSED
 BUILDING. PER FBC FUEL GAS SECTION *404.11 PIPING
 UNDERGROUND BENEATH BUILDINGS.
 PIPING INSTALLED UNDERGROUND BENEATH BUILDINGS IS
 PROHIBITED EXCEPT WHERE THE PIPING IS ENCASED IN A
 CONDUIT OF WROUGHT IRON, PLASTIC PIPE OR STEEL PIPE
 DESIGNED TO WITHSTAND THE SUPERIMPOSED LOADS. SUCH
 CONDUIT SHALL EXTEND INTO AN OCCUPIABLE PORTION OF THE
 BUILDING AND, AT THE POINT WHERE THE CONDUIT TERMINATES
 IN THE BUILDING, THE SPACE BETWEEN THE CONDUIT AND THE
 GAS PIPING SHALL BE SEALED TO PREVENT THE POSSIBLE
 ENTRANCE OF ANY GAS LEAKAGE. WHERE THE END SEALING IS
 CAPABLE OF WITHSTANDING THE FULL PRESSURE OF THE GAS
 PIPE, THE CONDUIT SHALL BE DESIGNED FOR THE SAME
 PRESSURE AS THE PIPE. SUCH CONDUIT SHALL EXTEND NOT
 LESS THAN 4 INCHES (102 MM) OUTSIDE THE BUILDING, SHALL
 BE VENTED ABOVE GRADE TO THE OUTDOORS AND SHALL BE
 INSTALLED SO AS TO PREVENT THE ENTRANCE OF WATER AND
 INSECTS. THE CONDUIT SHALL BE PROTECTED FROM CORROSION
 IN ACCORDANCE WITH SECTION 404.8 . CLEARLY INDICATE
 THIS REQUIREMENT ON THE RESUBMITTAL. PER FBC FUEL GAS
 SECTION *401.1 SCOPE.
  
 8. SHEET P-3 NATURAL GAS PIPING RISER: NOTES: 1)
 INDICATES THE FOLLOWING "CONTRACTOR TO SUBMIT A PROPER
 GAS PIPING LAYOUT WITH PERMIT APPLICATION". BY THE
 INDICATION OF THIS NOTE, IS IT THE INTENT TO HAVE THE
 PLUMBING OR GAS CONTRACTOR TO SUBMIT THEIR OWN DESIGN
 AT THE TIME OF THE GAS PERMIT APPLICATION? IF THAT IS
 THE INTENT PLEASE REMOVE ALL GAS PIPING DESIGN FROM
 SHEETS P-1 AND P-3 AS WELL AS THE PROPOSED GENERATOR
 AND CLEARLY INDICATE THE GENERATOR AS "FUTURE". PER
 CITY WPB AMENDMENTS SECTION *106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS AND SECTION *401.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  