2008-01-28 14:34:08 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| GAS PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET P-3 NATURAL GAS PIPING RISER: |
| SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE SECTION *401.1 SCOPE. |
| *THE GAS PIPING RISER DOES NOT INDICATE CORRESPONDING |
| LENGTHS TO ALL CUT SECTIONS OF PIPE. REFERENCE THE RED |
| CIRCLED CUT SECTIONS THAT ARE HIGH LIGHTED YELLOW. |
| |
| 2. SHEET P-3 NATURAL GAS PIPING RISER: |
| SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS |
| SECTION *401.1 SCOPE. |
| *THE GAS PIPING RISER DOES NOT INDICATE THE TYPE OF |
| PIPING MATERIAL BEING USED. |
| |
| 3. SHEET P-3 NATURAL GAS PIPING RISER: |
| SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| * THE ADDED SUM OF THE INDICATED CORRESPONDING LENGTHS |
| TO CUT SECTIONS OF PIPING EQUALS 151', HOWEVER NOTES: |
| 3) DISTANCE IS INDICATING 185'. PLANS AT A MINIMUM |
| SHALL BE CORRELATED. PER FBC FUEL GAS SECTION *401.1 |
| SCOPE. |
| |
| 4. SHEET P-3 NATURAL GAS PIPING RISER: |
| INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| * NOTES: 4) DELIVERY PRESSURE PRESSURE IS BEING |
| INDICATED AS 0.8 PSI. THIS INDICATED DELIVERY PRESSURE |
| IS WRONG FOR NATURAL GAS. FLORIDA PUBLIC UTILTIES CO. |
| HAS 0.5, 2 OR 5 PSI DELIVERY PRESSURE. |
| |
| 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| *PLEASE SUBMIT TWO COPIES OF MANUFACTURER |
| SPECIFICATIONS ON THE PROPOSED GENERATOR INDICATING THE |
| MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING |
| FROM A NATIONALLY RECOGNIZED TESTING LABORATORY AS WELL |
| AS INDICATING THE MANUFACTURER SETBACK RECOMMENDATIONS |
| FROM STRUCTURES. |
| |
| 6. SUBMIT TWO COPIES OF A SITE PLAN OR SURVEY CLEARLY |
| INDICATING THE LOCATION OF THE PROPOSED GENERATOR |
| INDICATING A DIMENTIONS FROM PROPERTY LINES AND |
| DISTANCES FROM STRUCTURES. (ZONING APPROVAL REQUIRED |
| FOR PROPOSED GENERATOR LOCATION PRIOR TO GAS PERMIT |
| BEING ISSUED) PER FBC FUEL GAS SECTION *401.1 SCOPE |
| |
| 7. SHEET P-1 GAS PLAN IS CLEARLY INDICATING WHERE THE |
| UNDERGROUND GAS PIPING IS BENEATH THE PROPOSED |
| BUILDING. PER FBC FUEL GAS SECTION *404.11 PIPING |
| UNDERGROUND BENEATH BUILDINGS. |
| PIPING INSTALLED UNDERGROUND BENEATH BUILDINGS IS |
| PROHIBITED EXCEPT WHERE THE PIPING IS ENCASED IN A |
| CONDUIT OF WROUGHT IRON, PLASTIC PIPE OR STEEL PIPE |
| DESIGNED TO WITHSTAND THE SUPERIMPOSED LOADS. SUCH |
| CONDUIT SHALL EXTEND INTO AN OCCUPIABLE PORTION OF THE |
| BUILDING AND, AT THE POINT WHERE THE CONDUIT TERMINATES |
| IN THE BUILDING, THE SPACE BETWEEN THE CONDUIT AND THE |
| GAS PIPING SHALL BE SEALED TO PREVENT THE POSSIBLE |
| ENTRANCE OF ANY GAS LEAKAGE. WHERE THE END SEALING IS |
| CAPABLE OF WITHSTANDING THE FULL PRESSURE OF THE GAS |
| PIPE, THE CONDUIT SHALL BE DESIGNED FOR THE SAME |
| PRESSURE AS THE PIPE. SUCH CONDUIT SHALL EXTEND NOT |
| LESS THAN 4 INCHES (102 MM) OUTSIDE THE BUILDING, SHALL |
| BE VENTED ABOVE GRADE TO THE OUTDOORS AND SHALL BE |
| INSTALLED SO AS TO PREVENT THE ENTRANCE OF WATER AND |
| INSECTS. THE CONDUIT SHALL BE PROTECTED FROM CORROSION |
| IN ACCORDANCE WITH SECTION 404.8 . CLEARLY INDICATE |
| THIS REQUIREMENT ON THE RESUBMITTAL. PER FBC FUEL GAS |
| SECTION *401.1 SCOPE. |
| |
| 8. SHEET P-3 NATURAL GAS PIPING RISER: NOTES: 1) |
| INDICATES THE FOLLOWING "CONTRACTOR TO SUBMIT A PROPER |
| GAS PIPING LAYOUT WITH PERMIT APPLICATION". BY THE |
| INDICATION OF THIS NOTE, IS IT THE INTENT TO HAVE THE |
| PLUMBING OR GAS CONTRACTOR TO SUBMIT THEIR OWN DESIGN |
| AT THE TIME OF THE GAS PERMIT APPLICATION? IF THAT IS |
| THE INTENT PLEASE REMOVE ALL GAS PIPING DESIGN FROM |
| SHEETS P-1 AND P-3 AS WELL AS THE PROPOSED GENERATOR |
| AND CLEARLY INDICATE THE GENERATOR AS "FUTURE". PER |
| CITY WPB AMENDMENTS SECTION *106.1.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS AND SECTION *401.1 SCOPE. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |