2008-01-23 15:33:55 
  
 ** DENIEDREVIEW **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2007 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2007 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 ** PLANS SHOW THE 1999 NFPA-70 AND A 2004 NFPA/LS 101
 WHICH DOES NOT EXIST. PLEASE ADJUST.
 PLEASE ALSO INCLUDE THE ABOVE RELEVANT CODES ON
 ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SUBMIT THE RELEVANT MANUFACTURES
 SPECS/CUT SHEETS FOR THE NEW PROPOSED GENERATOR AND
 TRANSFER SWITCH.
 PLEASE BE SURE THE MANUFACTURES SPECS/CUT SHEETS
 CONTAIN ALL THE MINIMUM CLEARANCE REQUIREMENTS. 110.3,
 90.7.
 FBC ADMIN SECTION 106.1.2
  
 3) NOTE: PLEASE INDICATE IF THE GENERATOR WILL BE A
 SEPARATELY DERIVED SYSTEM. PLEASE SEE
 250.20,250.66,250.30 ETC.
 PLEASE KNOW KOHLER AS STATED ON PLANS COME SHIPPED AS
 SD AND WILL REQUIRE REMOVAL OF BONDING JUMPER IF THIS
 IS NOT GOING TO BE SD.
  
 4) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCES FOR
 CU #2 AND #3, DISCONNECTS.
  
 5) NOTE: PLEASE SEE FBC R313 FOR REQUIRED NEW OR
 EXISTING SMOKE ALARMS IN THE EXISTING DWELLING MEETING
 CURRENT NFPA-72 11.5.1.1, AND 11.8.3.
 PLEASE SHOW LAYOUT OF ALL NEW TO BE INSTALLED OR
 EXISTING MEETING CURRENT CODES.
  
 6) NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSE, THE
 POOL SCOPE OF WORK WILL BE REQUIRED TO BE UNDER A
 SEPARATE PERMIT.
 106.1
  
 7) NOTE: PLEASE CLARIFY HEATING SYSTEMS. LOAD
 CALCULATIONS INDICATE *SPACE HEATERS* HOWEVER SHOULD
 THESE NO BE HEAT-STRIPS? SPACE HEATERS BY DEFINITION
 ARE NOT THE SAME AS CENTRAL HEAT.
 PLEASE ADJUST.
 FBC 106.3.5.4, NEC 424, 422
  
 8) NOTE: PLEASE SEE MISSING RECEPTACLE(S) PER 210.52,
 210.52H FOR FOYER/HALL AREA. PLEASE ALSO VERIFY WALL AT
 WHAT APPEARS TO BE HALL AREA #2 ON WALL SPACE ON THE
 BACK/UNDERSIDE OF COUNTER SPACE.
  
 9) NOTE: PLEASE SEE 410.8 FOR MINIMUM CLEARANCES FOR
 LIGHTING FIXTURES. THE TYPE OF FIXTURE NEEDS TO BE
 RELOCATED OR ADJUST TYPE OF FIXTURE.
  
 10) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE(S) FOR
 NEW CIRCUITS ARE TO BE SPECIFIC TO ROOMS AND AREAS IN
 WHICH THEY FEED. PLEASE SEE THE FOLLOWING TEXT WHICH IS
 TAKEN FROM THE CODE COMMENTARY.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 AS THE PANEL SCHEDULE MENTIONS GEN LTS AND RECEPTS IN
 MANY LOCATIONS, THESE WOULD BE FOR EXAMPLE: MEDIA ROOM,
 DINING RM LTS, DINING RM RECEPTS ETC.
 IT IS KNOWN TO THIS OFFICE THIS WILL BE REVISED BEFORE
 FINAL.
 FBC 106.1.2, 106.3.5.4,
  
 11) NOTE: PLEASE SEE FOUNTAIN LOCATION AT REAR OF
 DWELLING WHICH IS SWITCHED FROM INSIDE DOES NOT SHOW
 ANY GFI PROTECTION AS REQUIRED PER 210.8A3, 680.56
  
 12) NOTE: PLEASE SEE RISER IS MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM ALL LOCATIONS AFTER THE FIRST
 MEANS OF DISCONNECT PER 250.110, 250.24, 250.6, 250.122
 ETC
  
 13) NOTE: PLEASE SEE MISSING DISCONNECTING MEANS FOR
 FEEDERS FROM GENERATOR TO DWELLING.
 PLEASE SEE 225.31-225.39. PLEASE ALSO SEE 702.11 AS THE
 EXCEPTION OF THE DISCONNECTING MEANSMSUT MEET ALL
 REQUIREMENTS.
  
 14) NOTE: PLEASE SEE GROUNDING ELECTRODE SYSTEM IS
 SHOWING #4 AWG FOR GROUNDING ELECTRODE CONDUCTOR BEING
 PARALLELED WHICH IS NOT PERMITTED. PLEASE SEE 250.66
 FOR SIZING OF THE GROUNDING ELECTRODE CONDUCTOR. PLEASE
 SEE THE RISER ALSO SHOW *STRUCTURAL STEEL* AS PART OF
 THE GROUNDING ELECTRODE SYSTEM. STRUCTURAL STEEL WHERE
 PRESENT IS REQUIRED PER 250.50, HOWEVER PLEASE SEE
 250.50 AS FOOTER STEEL (NEW) IS ALSO REQUIRED.
 PLEASE ADJUST AND INCLUDE ON RISER.
  
 15) NOTE: PLEASE SEE THE SERVICE IS BEING SHOWN AS
 400AMPS YET THE METER CAN IS ONLY SHOWN AS 300AMPS. IS
 THIS A TRUE 300AMP METER CAN?
 PLEASE VERIFY AND ADJUST AS ALL SERVICE EQUIPMENT SHALL
 BE RATED FOR SIZING OF SERVICE.
 110.3, 90.7, 230, ETC
  
 16) NOTE: PLEASE VERIFY CIRCUITING FOR DINING ROOM
 RECEPTACLES PER 210.52B1, 210.11C1 AND 220.53. PLEASE
 SEE LOAD CALCULATIONS INDICATE 3-SMALL APPLIANCE
 CIRCUITS YET THE PANEL SCHEDULES ONLY SHOWS 2. PLEASE
 CLARIFY IF THIS OTHER CIRCUIT AS SHOWN IS THE DINING
 ROOM.
  
 17) NOTE: PLEASE VERIFY THE KW RATING OF THE GENERATOR.
 THE UNIT IS 30KW ON RISER AND 27KW IN NOTES.
 FBC 106.1.2 FOR COORDINATION.
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717