Plan Review Notes
Plan Review Notes For Permit 08010376
Permit Number 08010376
Review Stop E
Sequence Number 2
Notes
Date Text
2008-04-28 17:02:11** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 ** AS NOTED ON PREVIOUS REVIEW THERE MAY CERTAINLY BE
 NEW COMMENTS ONCE ALL INFORMATION IS SUBMITTED FOR
 REVIEW.
  
 1) NOTE: PLEASE SEE NO LIGHTING CONTROLS IN COMPLIANCE
 WITH FBC 13-415.1.ABC.1.1, .1.2 AND.1.3.
 PLEASE KNOW THIS BUILDING IS OVER 5K SQ FT AND IS
 REQUIRED TO CONTAIN AUTOMATED LIGHTING CONTROLS FOR ALL
 LIGHTING.
 AS NO SYSTEM OR LIGHTING CONTROLS DEVICES ARE SHOWN AT
 THIS TIME IN COMPLIANCE WITH THE FLORIDA BUILDING CODE
 CHAPTER 13 SECTIONS AS GIVEN ABOVE ARE NOT SHOWN NO
 REVIEW OF THESE ITEMS CAN BE DONE AT THIS TIME.
  
 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS AS REQUESTED ON PREVIOUS REVIEW IN
 COMPLIANCE WITH FBC 13-415.2.ABC.1.1, .1.2.
 PLEASE KNOW ALSO AS MENTIONED ABOVE MINIMUM CODE
 COMPLIANCE IS NOT YET SHOWN.
  
 3) NOTE: PLEASE SEE NOW PLANS SHOW CIRCUITING ETC
 HOWEVER CIRCUITS ON PANEL SCHEDULE NEED TO BE SPECIFIC
 TO AREAS AND ITEMS IN WHICH THEY FEED.
 408.4
  
 4) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER
 210.62
  
 5) NOTE: PLEASE SEE MISSING LOAD CALCULATIONS PER NEC
 220.
 PLEASE SEE LOADS FOR SHOW WINDOWS PER 220.43A
 PLEASE SEE LOADS FOR TRACK LIGHTING NEED TO BE SHOWN
 PER 220.43B.
 PLEASE SEE NO CONTINUOUS LOADS SHOWN AT 125% PER 215.3,
 230.42 ETC.
  
 6) NOTE: PLEASE SEE THE OWNER INFORMATION ON THE PERMIT
 APPLICATION NEEDS TO BE UPDATED AS THE OWNER IS NOT
 JOHNNY'S DREAM INC. THIS IS THE TENANTS NAME AND OWNER
 OF SAID BUILDING IS ATTACHED TO ELECTRICAL NOTES FOR
 INFORMATION. PLEASE ADJUST.
  
 7) NOTE: PLEASE INDICATE THE ELECTRICAL AND RELEVANT
 CODE ON ELECTRICAL SHEETS AS PREVIOUSLY NOTED.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-70
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 PLANS MAY BE RETAINED BY THIS OFFICE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]