2008-04-28 17:02:11 | ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING. |
| ** AS NOTED ON PREVIOUS REVIEW THERE MAY CERTAINLY BE |
| NEW COMMENTS ONCE ALL INFORMATION IS SUBMITTED FOR |
| REVIEW. |
| |
| 1) NOTE: PLEASE SEE NO LIGHTING CONTROLS IN COMPLIANCE |
| WITH FBC 13-415.1.ABC.1.1, .1.2 AND.1.3. |
| PLEASE KNOW THIS BUILDING IS OVER 5K SQ FT AND IS |
| REQUIRED TO CONTAIN AUTOMATED LIGHTING CONTROLS FOR ALL |
| LIGHTING. |
| AS NO SYSTEM OR LIGHTING CONTROLS DEVICES ARE SHOWN AT |
| THIS TIME IN COMPLIANCE WITH THE FLORIDA BUILDING CODE |
| CHAPTER 13 SECTIONS AS GIVEN ABOVE ARE NOT SHOWN NO |
| REVIEW OF THESE ITEMS CAN BE DONE AT THIS TIME. |
| |
| 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| CALCULATIONS AS REQUESTED ON PREVIOUS REVIEW IN |
| COMPLIANCE WITH FBC 13-415.2.ABC.1.1, .1.2. |
| PLEASE KNOW ALSO AS MENTIONED ABOVE MINIMUM CODE |
| COMPLIANCE IS NOT YET SHOWN. |
| |
| 3) NOTE: PLEASE SEE NOW PLANS SHOW CIRCUITING ETC |
| HOWEVER CIRCUITS ON PANEL SCHEDULE NEED TO BE SPECIFIC |
| TO AREAS AND ITEMS IN WHICH THEY FEED. |
| 408.4 |
| |
| 4) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER |
| 210.62 |
| |
| 5) NOTE: PLEASE SEE MISSING LOAD CALCULATIONS PER NEC |
| 220. |
| PLEASE SEE LOADS FOR SHOW WINDOWS PER 220.43A |
| PLEASE SEE LOADS FOR TRACK LIGHTING NEED TO BE SHOWN |
| PER 220.43B. |
| PLEASE SEE NO CONTINUOUS LOADS SHOWN AT 125% PER 215.3, |
| 230.42 ETC. |
| |
| 6) NOTE: PLEASE SEE THE OWNER INFORMATION ON THE PERMIT |
| APPLICATION NEEDS TO BE UPDATED AS THE OWNER IS NOT |
| JOHNNY'S DREAM INC. THIS IS THE TENANTS NAME AND OWNER |
| OF SAID BUILDING IS ATTACHED TO ELECTRICAL NOTES FOR |
| INFORMATION. PLEASE ADJUST. |
| |
| 7) NOTE: PLEASE INDICATE THE ELECTRICAL AND RELEVANT |
| CODE ON ELECTRICAL SHEETS AS PREVIOUSLY NOTED. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-70 |
| |
| 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE |
| COMPLIANCE. |
| THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| PLANS MAY BE RETAINED BY THIS OFFICE. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |