Plan Review Notes
Plan Review Notes For Permit 08010376
Permit Number 08010376
Review Stop M
Sequence Number 1
Notes
Date Text
2008-01-28 13:54:10PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS PAGE A-2 SHOWS ONE NEW SUPPLY AND RETURN AIR
 GRILL. PLEASE SHOW ON PLAN ALL NEW GRILL SIZES, DUCT
 (FLEX) SIZES AND CFM'S AT NEW SUPPLY AIR GRILLS. SEE
 2004 FBC 106.3.5.
  
 2) THE RESTROOMS REQUIRE EXHAUST FANS, SEE 2004 FBC/M
 403.2. PLEASE CORRECT, AND LIST AS NEW OR EXISTING.
  
 3) PLEASE ADD OUTSIDE AIR CALCULATIONS TO PLANS AND
 PROVIDE OUTSIDE AIR TO SPACE, SEE 2004 FBC/M 401.2.
  
 4) PLEASE SHOW ALL MECHANICAL WORK TO BE DONE AND LIST
 AS NEW OR EXISTING, SEE 2004 FBC 106.3.5.
  
 5) SEE ELECTRICAL REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]