2008-01-23 11:44:16 | |
| |
| ** DENIEDREVIEW ** |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2007 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2007 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLANS DO NOT CONTAIN ANY MINIMUM CODES FOR REQUIRED |
| DESIGNS. |
| |
| 2) NOTE: PLEASE SEE PLANS SUBMITTED ARE MISSING |
| COMPLETED INFORMATION ON TITLE BLOCKS FOR DESIGN FIRM |
| AND PROFESSIONAL(S) PER FLORIDA ADMINISTRATIVE CODE |
| 61G1-16.004, 61G15-23.002, AND FLORIDA STATUTES |
| 481.219, 471.023. |
| ** PLEASE KNOW AS NO INFORMATION WAS SHOWN FOR SECTIONS |
| ABOVE, NO REVIEW COULD BE DONE BASED ON ANY DESIGN |
| PROFESSIONAL. |
| |
| 3) NOTE: PLEASE SEE PLANS ARE NOT SIGNED, DATED AND |
| SEALED AS REQUIRED PER FS 481.221, 471.025. |
| ** NO REVIEW OF STATUTORY REQUIREMENTS COULD BE DONE. |
| |
| 4) NOTE: PLEASE BE SURE THE SUITE/UNIT NUMBER IS PLACED |
| ON TITLE BLOCKS. |
| FAC 61G1-16.004, 61G15-23.002, FBC ADMIN SECTION, |
| 106.5, 106.1.2 ETC |
| |
| 5) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS WITH |
| MINIMUM COMPLIANCE WITH THE 2005 NFPA-70 (NATIONAL |
| ELECTRICAL CODE). |
| PLEASE SHOW ALL CIRCUITING ON PLANS AND CORRELATE WITH |
| PANEL SCHEDULE(S), BRANCH CIRCUITS, OVER CURRENT |
| PROTECTION DEVICES, MINIMUM CIRCUITS, LOAD |
| CALCULATIONS, SIGN CIRCUIT(S), SHOW WINDOWS ETC ETC. |
| ** PLEASE KNOW AS PLANS DO NOT CONTAIN ANY MINIMUM |
| ELECTRICAL REQUIRED INFORMATION OR DESIGN PER THE |
| NATIONAL ELECTRICAL CODE, NO REVIEW FOR ANY OF THESE |
| COULD BE DONE AT THIS TIME. |
| THERE MAY CERTAINLY BE NEW COMMENTS UPON THE NEXT |
| REVIEW WHICH COULD NOT MADE AT THIS TIME. |
| PLEASE SEE ALL OF THE 2005 NEC. |
| 210, 230, 240, 220, 310.16, 408.4, 250, 600.5, ETC |
| THERE ARE TOO MANY CODE SECTIONS TO MENTION. |
| |
| 6) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2 FOR |
| MINIMUM COMPLIANCE FOR LIGHTING PERFORMANCE |
| CALCULATIONS TO BE SUBMITTED. |
| PLEASE SEE COMMENTS FROM OTHER TRADES SUCH AS |
| MECHANICAL REVIEW WHICH WILL AFFECT CHAPTER 13 |
| REQUIREMENTS. |
| |
| 7) NOTE: PLEASE SUBMIT MINIMUM COMPLIANCE WITH FBC |
| CHAPTER 13 , 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| PLEASE KNOW AS NO MINIMUM DESIGN FOR CODE COMPLIANCE |
| WAS SHOWN ON PLANS, NO REVIEW OF ANY OF THESE ITEMS |
| COULD BE DONE AT THIS TIME. |
| |
| ** PLEASE KNOW AS THERE IS MUCH INFORMATION NOT YET |
| DESIGNED OR SUBMITTED FOR REVIEW THERE MAY VERY WELL BE |
| NEW COMMENTS ON THE NEXT REVIEW WHICH CAN NOT BE MADE |
| AT THIS TIME. |
| |
| ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| CONTACTING THIS REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |