Plan Review Notes For Permit 08010343 |
Permit Number |
08010343 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-03-04 14:50:21 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) SEE ENERGY CALCULATIONS HAVE THE WRONG ADDRESS ON | | THEM AND ARE THE JURISDICTION INFORMATION ON THEM, | | PLEASE CORRECT, PER 2004 FBC 13-600.3.A. | | | | 2) SEE ENERGY CALCULATIONS LINE 6 SHOWS 864 SQ. FT. | | UNDER AIR. THE ADDITION IS 490 SQ. FT. UNDER AIR, | | PLEASE CORRECT (YOU MAY SUBMIT THE SHORT FORM 600C-04R | | FOR LESS THAN 600 SQ. FT. UNDER AIR. SEE 2004 FBC | | 13-600.3.C. | | | | 3) SEE ENERGY CALCULATIONS LINE 9A AND B ARE SHOWING | | THE WALLS TO BE CONCRETE WITH R-4.1 INSULATION, THE | | PLANS SHOW THE WALLS TO BE 2X4 WOOD WITH R-11 | | INSULATION, PLEASE CORRECT ENERGY CAL'S. PER 2004 FBC | | 13-6003.A. | | | | 4) SEE ENERGY CAL'S. LINE 12A AND B ARE SHOWING THREE | | DIFFERENT A/C SYSTEMS, THE PLANS SHOW ONLY ONE NEW WALL | | UNIT BEING INSTALLED IN THE ADDITION, PLEASE CORRECT | | ENERGY CAL'S PER 2004 FBC 13-600.3.A. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|