Plan Review Notes
Plan Review Notes For Permit 08010343
Permit Number 08010343
Review Stop P
Sequence Number 1
Notes
Date Text
2008-01-28 16:21:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 19 PLUMBING PLAN AND SANITARY RISER DIAGRAM
 BATHROOM #1: SHOWER NOT VENTED. PER FBC PLUMBING
 SECTION *901.2.1 VENTING REQUIRED.
  
 2. SHEET 19 PLUMBING PLAN AND SANITARY RISER DIAGRAM
 BATHROOM #2: TUB IS MISLABELED AS A SHOWER AND IS NOT
 VENTED. PER CITY WPB AMENDMENTS SECTION *106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS AND FBC PLUMBING
 SECTION *901.2.1 VENTING REQUIRED.
  
 3. SHEET 19 PLUMBING PLAN: PLEASE CORRECT THE SPELLING
 OF "RAISER" TO "RISER". PER CITY WPB AMENDMENTS SECTION
 *106.1.1 INFORMATION ON CONSRTRUCTION DOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]