 ** DENIEDREVIEW **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2007 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2007 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 ** PLANS SHOW THE 2002 NFPA-70
  
 2) NOTE: PLEASE SEE PLANS DO NOT CONTAIN ANY
 INFORMATION, SIGNATURE, PRINTED NAME FOR ANY DESIGN
 PROFESSIONAL AS REQUIRED PER FAC, FBC ADMIN SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH 106.5, 106.1.2.
 FS 481.229, 471.003 OR 468.
 PLEASE SEE EXCEPTIONS IN 481.229 AND 471.003.
  
 3) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS THE SMOKE
 DETECTION DEVICES NOTED ON PLANS ARE SHOWN AND NOTED A
 *SMOKE DETECTORS*. SMOKE DETECTORS ONLY DETECT AND DO
 NOT SOUND AND ALARM. PLEASE SEE DEFINITION OF SMOKE
 ALARMS AS STATED IN NFPA-72 AND FBC R313.
 PLANS MENTIONS SD, WHERE THIS SEEMS TO BE THESE SHOULD
 BE SA.
 PLEASE ADJUST.
 PLEASE SEE NFPA-72 11.5.1.1 FOR LOCATIONS REQUIRED.
 PLEASE SEE MISSING SA OUTSIDE MASTER SLEEPING ROOM.
  
 4) NOTE: PLEASE SEE THE LIGHTING CONTROL FOR EGRESS
 FROM THE MASTER BEDROOM HALLWAY NEEDS TO BE LOCATED
 INSIDE THAT HALLWAY BEFORE EGRESS OUT OF THE REAR PATIO
 DOOR.
 PLEASE RELOCATE SWITCH.
 210.70, LS 101 7.8
  
 5) NOTE: PLEASE SEE MISSING RECEPTACLE PER 210.52 ON
 MASTER BEDROOM WALL WHICH IS GREATER THAN 2FT.
  
 6) NOTE: PLEASE SEE MINIMUM OVER CURRENT PROTECTION FOR
 THE 10KE HEAT-STRIP SHALL BE SIZED AT A MINIMUM OF 125%
 PER 424.3B.
  
 7) NOTE: PLEASE LIST ALL ITEMS ON PANEL SCHEDULE WHICH
 ARE NEW OR ALREADY EXISTS.
 PLEASE SEE SOME ITEMS ARE LABELED AS NEW HOWEVER NOT
 ALL.
 FOR EXAMPLE: WATER HEATER, WASHER, DRYER ETC.
 THIS ITEMS ARE SHOWN AS NEW ON PLANS.
 408.4.
 FBC 106.3.5.4
  
 8) NOTE: PLEASE SEE ELECTRICAL PLANS DOES INDICATE A
 NEW A/C WALL UNIT HOWEVER THERE IS NO DEDICATE CIRCUIT
 OR LOAD SHOWN ON PANEL SCHEDULE.
 240.4, 408.4, 310.16, 220 ETC
 PLEASE BE SURE TO SEE 210.12 FOR REQUIRED AFCI
 PROTECTION OF THIS UNIT.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]