2008-01-23 12:53:42 | |
| |
| ** DENIEDREVIEW ** |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2007 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2007 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| |
| ** PLANS SHOW THE 2002 NFPA-70 |
| |
| 2) NOTE: PLEASE SEE PLANS DO NOT CONTAIN ANY |
| INFORMATION, SIGNATURE, PRINTED NAME FOR ANY DESIGN |
| PROFESSIONAL AS REQUIRED PER FAC, FBC ADMIN SECTION AS |
| ADOPTED BY THE CITY OF WEST PALM BEACH 106.5, 106.1.2. |
| FS 481.229, 471.003 OR 468. |
| PLEASE SEE EXCEPTIONS IN 481.229 AND 471.003. |
| |
| 3) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS THE SMOKE |
| DETECTION DEVICES NOTED ON PLANS ARE SHOWN AND NOTED A |
| *SMOKE DETECTORS*. SMOKE DETECTORS ONLY DETECT AND DO |
| NOT SOUND AND ALARM. PLEASE SEE DEFINITION OF SMOKE |
| ALARMS AS STATED IN NFPA-72 AND FBC R313. |
| PLANS MENTIONS SD, WHERE THIS SEEMS TO BE THESE SHOULD |
| BE SA. |
| PLEASE ADJUST. |
| PLEASE SEE NFPA-72 11.5.1.1 FOR LOCATIONS REQUIRED. |
| PLEASE SEE MISSING SA OUTSIDE MASTER SLEEPING ROOM. |
| |
| 4) NOTE: PLEASE SEE THE LIGHTING CONTROL FOR EGRESS |
| FROM THE MASTER BEDROOM HALLWAY NEEDS TO BE LOCATED |
| INSIDE THAT HALLWAY BEFORE EGRESS OUT OF THE REAR PATIO |
| DOOR. |
| PLEASE RELOCATE SWITCH. |
| 210.70, LS 101 7.8 |
| |
| 5) NOTE: PLEASE SEE MISSING RECEPTACLE PER 210.52 ON |
| MASTER BEDROOM WALL WHICH IS GREATER THAN 2FT. |
| |
| 6) NOTE: PLEASE SEE MINIMUM OVER CURRENT PROTECTION FOR |
| THE 10KE HEAT-STRIP SHALL BE SIZED AT A MINIMUM OF 125% |
| PER 424.3B. |
| |
| 7) NOTE: PLEASE LIST ALL ITEMS ON PANEL SCHEDULE WHICH |
| ARE NEW OR ALREADY EXISTS. |
| PLEASE SEE SOME ITEMS ARE LABELED AS NEW HOWEVER NOT |
| ALL. |
| FOR EXAMPLE: WATER HEATER, WASHER, DRYER ETC. |
| THIS ITEMS ARE SHOWN AS NEW ON PLANS. |
| 408.4. |
| FBC 106.3.5.4 |
| |
| 8) NOTE: PLEASE SEE ELECTRICAL PLANS DOES INDICATE A |
| NEW A/C WALL UNIT HOWEVER THERE IS NO DEDICATE CIRCUIT |
| OR LOAD SHOWN ON PANEL SCHEDULE. |
| 240.4, 408.4, 310.16, 220 ETC |
| PLEASE BE SURE TO SEE 210.12 FOR REQUIRED AFCI |
| PROTECTION OF THIS UNIT. |
| |
| ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| CONTACTING THIS REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |