Date |
Text |
2008-01-28 12:15:13 | 2004 FBC W/2007 REVISIONS |
| ADDITION AND LEVEL 2 ALTERATIONS |
| |
| DENIED BY BUILDING |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3)SUBMIT ENERGY CALCULATIONS AS REQUIRED BY 2004 FBC |
| SECTION 13-6. NOTE: IN ADDITION TO THE SIGNATURE OF THE |
| PREPARER, THE OWNER/AGENT IS ALSO REQUIRED TO SIGN AND |
| DATE THE FORM. |
| |
| 4) SHOW COMPLIANCE OF THE BATHROOM WINDOWS WITH R308.4 |
| HAZARDOUS LOCATIONS. |
| THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS |
| LOCATIONS FOR THE PURPOSES OF GLAZING : 5. GLAZING |
| IN DOORS AND ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, |
| SAUNAS, STEAM ROOMS, BATHTUBS AND SHOWERS. GLAZING IN |
| ANY PART OF A BUILDING WALL ENCLOSING THESE |
| COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE |
| GLAZING IS LESS THAN 60 INCHES (1524 MM) MEASURED |
| VERTICALLY ABOVE ANY STANDING OR WALKING SURFACE. |
| |
| 5) PLEASE UPDATE THE CODE EDITION ON SHEETS 1 AND 2. |
| THE CURRENT CODE IS THE 2004 FBC W/2007 REVISIONS. |
| |
| 6) THE FOUNDATION NOTES ON SHEET 6 SPECIFY 2500 PSF AS |
| THE REQUIRED SOIL BEARING CAPACITY AND THE DETAILS ON |
| SHEETS 6,7,8,15 AND 16 SPECIFY THE SOIL COMPACTION AS |
| 2000 PSF. PLEASE CORRECT. 2004 FBC 106.1.1* CITY |
| AMENDMENTS |
| |
| 7) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR |
| TERMITES. |
| IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE |
| INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS |
| AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING |
| SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS: |
| 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS |
| THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE |
| MASONRY FOUNDATION SIDEWALL. |
| 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE |
| INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH |
| RAMPS ONLY. |
| 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO |
| AND GARAGE SLABS AND ENTRY AREAS. |
| |
| 8) THE FOOTING SCHEDULE ON SHEET 6 REFERS DETAILS ON |
| PAGE 6, HOWEVER, THESE FOOTING DETAILS ARE ON SHEET 7. |
| PLEASE CORRECT |
| |
| 9)THE KCC AND KECC COLUMN CAP CONNECTORS ARE |
| INCORRECTLY SPECIFIED AS SIMPSON PRODUCTS AND THEY ARE |
| MADE BY USP. THE UPLIFT VALUES ARE ALSO INCORRECT. THE |
| KCC 44 HAS UPLIFT OF 3920 AND KECCLL HAS UPLIFT OF |
| 1750. SEE LATEST USP CATALOG OR THEIR WEBSITE. |
| |
| 10) SUBMIT THE INSTALLATION DRAWINGS FOR THE STORM |
| PANLES AS REQUIRED BY FAC RULE 9B-72. SPECIFY THE MOUNT |
| TYPE, THE ANCHOR TYPE, ANCHOR SPACING, EDGE DISTANCE BY |
| CIRCLING THE APPROPRIATE ITEMS ON THE INSTALLATION |
| DRAWINGS AND TABLES. |
| |