2008-01-31 17:00:33 | RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST. REVIEW |
| UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION |
| IS TOO LOW. IT WAS UPDATED TO $6,274AS REQUIRED BY |
| SEC. 108.3 CITY AMENDMENTSTO FBC 2004.OWES $77.43 |
| FOR UPDATED PERMIT VALUATION AND RADON FEES. |
| |
| 2-PLEASE COORDINATEWITH ZONING TO SEE IF PROPOSED |
| PORCH MEETS THE REQUIRED SETBACKS. |
| |
| 3- PROVIDE COMPLETE SET OF CONSTRUCTION DRAWINGS |
| SHOWING ALL THE DESIGN CRITERIA REQUIRED BY SEC. R301.1 |
| OF 2004 FLORIDA RESIDENTIAL CODE.NEED TO SPECIFY ALL |
| LIVE LOADS, DEAD LOADS, WIND LOADS AND UPLIFT LOADS. |
| PROVIDECOMPLETE FOUNDATION PLAN,FLOOR PLAN AND ROOF |
| FRAMING PLAN. SPECIFY ALLSTRUCTURAL MEMBERS SIZES AND |
| CONNECTIONS. |
| |
| 4- PERSON RESPONSIBLE FOR THE DESIGNNEEDS TO PROVIDE |
| NAME AND SIGNATURE IN ALL DRAWINGS.IF ARCHITECT OR |
| ENGINEER IS RESPONSIBLE FOR THE DESIGN, THENSIGN AND |
| SEAL DRAWINGS AS REQUIRED BY CHAPTER 481 AND 471 |
| RESPECTIVELY. SEC. 106.1 CITY AMENDMENTS TO FBC 2004. |
| |
| 5- SPECIFY ROOF PITCH TO VERIFY COMPLIANCE WITH SLOPE |
| REQUIRED FOR ROOF SHINGLES SEC. R905.2.2 OF 2004 |
| FLORIDA RESIDENTIAL CODE. |
| |
| 6- SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE |
| FOR MINIMUMTYPE AND SPACING OF NAIL REQUIRED FOR ROOF |
| SHEATHING INSTALLATION. INCLUDING ON ROOF ZONE 3. |
| |
| 7- SPECIFY ATTACHMENT OF PROPOSED PORCH TO EXISTING |
| STRUCTURE TO VERIFY COMPLIANCE WITHTHE CALCULATED |
| WIND LOADS AS REQUIRED BY SEC. R301.1 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| NOTE:TAKE INTO CONSIDERATION THAT THIS IS A MOBILE |
| HOME AND PROPOSED PORCH WILL AFFECT THE STRUCTURAL |
| STABILITY OF THE MAIN HOUSE. |
| |
| 8- PROVIDE PRODUCT APPROVAL(2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) ROOF SHINGLES. |
| |
| B) ALL STRUCTURALCONNECTORS (SIMPSON OR USP) |
| SPECIFIED ON PLANS AND DETAILS. |
| |
| 9- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND |
| APPROVED IN WRITING(NOT SIGNING AND SEALING)BY THE |
| DESIGNER OF RECORD AS REQUIRED BY SEC. 106.3.3 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |